Checking The Air And Gas Pressure On The Combustion Head; Safety Components - Riello RS 200/E FGR Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

Clean UV sensor
Periodically clean the bulb to ensure correct operation of the UV
sensor.
Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
Gas filter
Replace the gas filter when it is dirty.
Flame inspection window
Clean the glass of the flame inspection window.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics intact,
especially the flue gas temperature and combustion chamber
pressure.
Combustion
If the combustion values found at the start of the intervention do
not satisfy current standards or anyway indicate a poor state of
combustion (consult the table below), contact the Technical As-
sistance Service for the necessary adjustments.
EN 676
Max. output
Theoretical
max. CO
GAS
2
0 % O
2
G 20
11.7
Gaskets
It is advisable to replace at each opening the following seals:
1 - gasket between shell and motor
2 - gasket between shell and fairing
3 - gaskets between casing and pipe coupling
4 - gasket between pipe coupling and front piece
1
2
20186077
1
Air excess
Max. output
  1.2
  1.3
CO
% Calibration
2
mg/kWh
 = 1.3
 = 1.2
9.7
9
3
20186080
Maintenance
7.2.4
Checking the air and gas pressure on the
combustion head
To carry out this operation a pressure gauge must be used to
measure the air and gas pressure at the combustion head, as
shown in Fig. 37.
Checking
gas pressure
+
_
Fig. 35
7.2.5

Safety components

The safety components should be replaced at the end of their life
cycle indicated in the following table.
The specified life cycles do not refer to the warranty terms indi-
cated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
CO
Gas valves (solenoid)
Pressure switches
 100
Pressure adjuster
Tab. N
Servomotor (electronic
cam)(if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic)(if present)
Flexible hoses (if present)
Fan impeller
4
Fig. 36
41
GB
20186214
+
_
Checking
air pressure
Fig. 37
Life cycle
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
15 years
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years
5 years or 30.000 pressurised
cycles
10 years or 500.000 start-ups
Tab. O
20171664

Advertisement

Table of Contents
loading

This manual is also suitable for:

20171518

Table of Contents