COMFORT-AIRE Century VMH-SV Series Service Manual page 152

Single-multi zone mini-split
Table of Contents

Advertisement

8.4 4-way Valve Check
1. Power on, use a digital tester to measure the voltage, when the unit operates in cooling, it is 0V. When the unit
operates in heating, it is about 230VAC.
If the value of the voltage is not in the range, the PCB must have problems and need to be replaced.
2 Turn off the power, use a digital tester to measure the resistance. The value should be 1.8~2.5 KΩ.
Troubleshooting
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents