Operator Programing Errors
An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an
individual parameter setting is inappropriate. This monitor will display the parameter that is
causing the OPE error.
LED Operator
Display
oPE01
Drive capacity and value set to o2-04 do not
match.
oPE02
Parameters were set outside the allowable setting
range.
A contradictory setting is assigned to multi-func-
tion contact inputs H1-01 through to H1-05.
• The same function is assigned to two inputs
oPE03
(this excludes "External fault" and "Not used")
• Input functions which require the setting of
other input functions were set alone.
• Input functions that are not allowed to be used
simultaneously have been set.
No option unit is installed and one of the follow-
oPE05
ing is true:
• b1-01=2 or 3
• b1-02=2
oPE10
The V/f pattern setting is incorrect.
YASKAWA Electric TOEP C710606 27 AC Drive - J1000 Quick Start Guide
Cause
7 Troubleshooting
Corrective Action
Correct the value set to o2-04.
Set parameters to the proper values.
• Fix any incorrect settings.
• Refer to the instruction manual for more details.
• Install the required option unit.
• Correct the values set to b1-01 and b1-02.
• Check the V/f pattern settings.
• Refer to the instruction manual for more details.