YASKAWA CIMR-JC Quick Start Manual page 25

Advertisement

Par.
Name
1:2.0 kHz
2:5.0 kHz
3:8.0 kHz
Carrier Fre-
4:10.0 kHz
C6-02
quency
5:12.5 kHz
Selection
6:15.0 kHz
7:Swing PWM
F: User defined
Frequency References
d1-01
Frequency
Set the multi-speed references 1 to
to
Reference
8
d1-08
1 to 8
d1-17 Jog Speed
Jog speed
V/f Pattern
Input
E1-01
Voltage Set-
Input Voltage
ting
For a linear V/f characteristics, set
Max.
Out-
E1-04
the same values for E1-07 and E1-
put Freq.
09. In this case, the setting for E1-
Max.
Out-
08 will be disregarded.
E1-05
put Voltage
Ensure that the four frequencies are
set according to these rules or
Base
Fre-
OPE10 fault will occur:
E1-06
quency
E1-04 ≥ E1-06 ≥ E1-07 ≥ E1-09
Middle Out-
E1-07
put Freq.
(E1-05)
Mid.
Out-
E1-08
put Voltage
Min.
Out-
E1-09
put Freq.
(E1-08)
(E1-10)
Min.
Out-
E1-10
put Voltage
Motor Data
Motor
E2-01
Rated
Motor rated current in Ampere.
Current
Motor
E2-02
Motor rated slip in hertz (Hz).
Rated Slip
YASKAWA Electric TOEP C710606 27 AC Drive - J1000 Quick Start Guide
Description
Output voltage
(E1-09)
(E1-07)
(E1-06)
Output frequency
Par.
Name
Motor
E2-03
No-Load
Current
Motor Line-
E2-05
to-Line
Resistance
DI S1 to
H1-01
S5
to
Function
H1-05
Selection
A list of the major functions can be found at the table end.
DO
H2-01
MA/MB
Function
Major functions are listed at the end of the table.
A1 Signal
H3-01
Level Sel.
H3-03 A1 Gain
H3-04 A1 Bias
AM
H4-01
Monitor
Selection
H4-02 AM Gain
H4-03 AM Bias
(E1-04)
Motor
L1-01
Overload
Prot. Sel.
Motor
L1-02
Overload
Prot. Time
6 Parameter Table
Description
Magnetizing current in Ampere.
Sets the phase-to-phase motor
resistance in ohms.
Digital Input Settings
Selects the function of terminals S1
to S5.
Digital Output Settings
Set the function for the relay output
MA-MB-MC.
Analog Input Setting
0:0 to +10 V (neg. input is zeroed)
1:0 to +10 V (bipolar input)
2:4~20mA (9 bit input)
3:0~20mA
Sets the input value in % at 10 V/
20 mA analog input.
Sets the input value in % at 0 V/0
mA/4 mA analog input.
Analog Input Setting
Enter value equal to U1-
monitor values. Example: Enter
"103" for U1-03.
Sets terminal AM output voltage
equal to 100% monitor value.
Sets terminal AM output voltage
equal to 0% monitor value.
Motor Overheat Protection
Sets the motor overload protection.
0:Disabled
1:Standard fan cooled motor
2:Standard blower cooled motor
Sets the motor overload protection
time in min. Normally no change is
necessary.
EN25