DMP Electronics 1100XH Series Installation And Programming Manual

High power wireless receiver
Hide thumbs Also See for 1100XH Series:

Advertisement

INSTALLATION AND PROGRAMMING GUIDE
1100XH Series
High Power Wireless Receiver

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1100XH Series and is the answer not in the manual?

Questions and answers

Summary of Contents for DMP Electronics 1100XH Series

  • Page 1 INSTALLATION AND PROGRAMMING GUIDE 1100XH Series High Power Wireless Receiver...
  • Page 2: Get Started

    GET STARTED The 1100XH Series High Power Wireless Receiver provides up to 100 wireless zones for XR150 Series panels and up to 500 wireless zones for XR550 Series panels. The 1100XHE features 128-bit AES encryption. The 1100XH provides two-way, supervised communication using 900 MHz frequency hopping-spread-spectrum technology.
  • Page 3: Installation

    INSTALLATION Program the Panel Refer to the panel programming guide as needed. Reset the panel. At a keypad, enter 6653 (PROG) to access the PROGRAMMER menu. In SYSTEM OPTIONS, program a HOUSE CODE between 1 and 50. See House Code Explained for more information.
  • Page 4: Wire The Receiver

    Wire the Receiver The panel immediately recognizes the 1100XH if the panel is programmed with a house code. Do not use shielded wire between the panel and receiver. Connect the red, yellow, green, and black wires to the PANEL terminal on the 1100XH. Connect the other end of the wires to the XBUS on the panel.
  • Page 5: Additional Information

    ADDITIONAL INFORMATION Wiring Specifications for X-Bus DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do Not use twisted pair or shielded wire for LX-Bus and Keypad Bus data circuits. To maintain auxiliary power integrity when using 22-gauge wire do not exceed 500 feet.
  • Page 6: Transmitter Supervision Time

    Transmitter Supervision Time For listed installations, program the transmitter supervision time in panel zone programming as listed in the following table. Refer to the panel programming guide for complete wireless programming information. UL LISTING LISTED ACCESSORIES SUPERVISION TIME 1164 Synchronized Smoke Detector UL 268 Smoke-Automatic Fire Detectors 1164NS Smoke Detector with No Sounder 1168 Wireless Smoke/CO/Low Temp Detector...
  • Page 7: Ordering Information

    LISTED COMPLIANCE SPECIFICATIONS For applications that must conform to a National Recognized Testing Laboratory certified system, read the information below for additional information. Commercial Fire Transmitters must be programmed as supervised. Refer to Table 3 for specific supervision times. The maximum line impedance of the 4-wire bus is 16.2 Ohms for 1,000 feet (305 meters).
  • Page 8: Fcc Information

    CERTIFICATIONS ▶ California State Fire Marshal (CSFM) New York City (FDNY) ▶ ▶ FCC Part 15 Registration ID: CCKPCO114R6 CCKPC0114R9 CCKPC0245 ▶ Industry Canada: 5251A-PC0114R6 5251A-PC0114R9 5251A-PC0245 Underwriters Laboratory (UL) Listed ANSI/UL 365 Police Station Connected Burglar ANSI/UL 609 Local Burglar Alarm Units & Systems ANSI/UL 864 Fire Protective Signaling Systems ANSI/UL 985...

This manual is also suitable for:

Xr150Xr5501100xh-w1100xhe-w

Table of Contents