Procedure Of Troubleshooting - Gree SAP24HP230V1A Service Manual

Hide thumbs Also See for SAP24HP230V1A:
Table of Contents

Advertisement

Service Manual

9.2 Procedure of Troubleshooting

Indoor unit
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process:
Installation and Maintenance
Start
Is the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
No
Is there short circuit due to trip-
over of the parts
No
Is the temperature sensor normal
according to the resistance table?
Yes
No
Replace the mainboard with
the same model.
End
Yes
Insert the temperature
sensor tightly
No
Is malfunction
eliminated
Yes
Make the parts upright
No
Is malfunction
eliminated
No
Replace it with a
temperature sensor with
the same model
Is malfunction
eliminated
Yes
Yes
Yes
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sap18hp230v1a

Table of Contents