Gree SAP24HP230V1A Service Manual page 59

Hide thumbs Also See for SAP24HP230V1A:
Table of Contents

Advertisement

in the holes.
(3) Fix the wall-mounting frame on the wall with tapping screws
(ST4.2X25T��������������������������
pulling the frame. If the plastic expansion particle is loose,
�������������������
3. Install Wall-mounting Frame
(1) Choose the position of piping hole according to the direction
of outlet pipe. The position of piping hole should be a little
lower than the wall-mounted frame.(As show in Fig.1)
Wall
Mark in the middle of it
Space
to the
wall
above
150mm
Left
˘55(70)mm
Rear piping hole
(2) Open a piping hole with the diameter of 2 3/16 or 2 3/4inch
on the selected outlet pipe position.In order to drain smoothly,
slant the piping hole on the wall slightly downward to the
outdoor side with the gradient of 5-10°.(As show in Fig.2)
Indoor
°
5-10
Note:
(1) Pay attention to dust prevention and take relevant safety
measures when opening the hole.
(2) The plastic expansion particles are not provided and should
be bought locally.
4. Outlet Pipe
(1) The pipe can be led out in the direction of right, rear right,
left or rear left.(As show in Fig.3)
(2) When selecting leading out the pipe from left or right, please
cut off the corresponding hole on the bottom case.(As show in
Fig.4)
right
Fig.3
Left
Cut off
the hole
56
.
Level meter
Space
to the
wall
above
150mm
Right
˘55(70)mm
Fig.1
Rear piping hole
Outdoor
2 3/16 or 2 3/4 inch
ˆ
Fig.2
rear left
Right
Fig.4
5. Connect the Pipe of Indoor Unit
(1) Aim the pipe joint at the corresponding bellmouth.(As show
in Fig.5)
(2) Pretightening the union nut with hand.
(3) Adjust the torque force by referring to the following sheet.
Place the open-end wrench on the pipe joint and place the
torque wrench on the union nut. Tighten the union nut with
torque wrench.(As show in Fig.6)
(4) Wrap the indoor pipe and joint of connection pipe with
insulating pipe, and then wrap it with tape.(As show in Fig.7)
Wall
Pipe joint
Union nut
Refer to the following table for wrench moment of force:
Hex nut diameter(inch)
6. Install Drain Hose
(1) Connect the drain hose to the outlet pipe of indoor unit.(As
show in Fig.8)
(2) Bind the joint with tape.(As show in Fig.9)
.
Fig.8
Note:
(1) Add insulating pipe in the indoor drain hose in order to
prevent condensation.
(2) The plastic expansion particles are not provided.
(As show in Fig.10)
Pipe
Torque wrench
Fig.5
Indoor pipe
Insulating pipe
Tightening torque(ft·Ibf)
Φ1/4
11.10~14.75
Φ3/8
20.12~29.50
Φ1/2
33.19~40.56
Φ5/8
44.24~47.94
Φ3/4
51.32~55.31
Outlet pipe
Tape
Outlet pipe
D
rain hose
Drain hose
Insulating pipe
Fig.10
Installation and Maintenance
Service Manual
Open-end
wrench
Union nut
Pipe
Fig.6
Fig.7
Drain hose
Fig.9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sap18hp230v1a

Table of Contents