Danfoss FC 100 Operating Instructions Manual page 52

Table of Contents

Advertisement

VLT® FC 100 LonWorks
8-05 End-of-Timeout Function
Option:
[0]
Hold set-up
[1] *
Resume set-up
8-06 Reset Control Timeout
Option:
[0] *
Do not reset
[1]
Do reset
8-07 Diagnosis Trigger
Option:
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
8-10 Control Profile
Option:
[0] *
FC profile
8-50 Coasting Select
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par.8-01
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the bus.
Option:
[0]
Digital Input
Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
Control Timeout Function
only when par.8-04
Retains the set-up selected in par.8-04
Reset Control Timeout
8-06
toggles. Then the frequency converter resumes its original set-up.
Resumes the set-up active prior to the time-out.
Function:
This parameter is active only when the choice
of-Timeout Function
.
Retains the set-up specified in par.8-04
control time-out.
Returns the frequency converter to the original set-up following a control word time-out. When the
Do reset
value is set to
[1], the frequency converter performs the reset and then immediately reverts
to the
Do not reset
[0] setting.
Function:
This parameter has no function for LonWorks.
Function:
Select the interpretation of the control and status words corresponding to the installed fieldbus.
Only the selections valid for the fieldbus installed in slot A will be visible in the LCP display.
Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
Activates Start command via the serial communication port or fieldbus option.
Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
Control Site
Digital and control word
is set to [0]
Function:
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
is set to [Set-up 1-4].
Control Timeout Function
and displays a warning, until par.
Hold set-up
[0] has been selected in par.8-05
Control Timeout Function
, [Select setup 1-4] following a
.
8 Parameters
End-
8
51