MA-1000
3
GENERAL DESCRIPTION
MA-1000 control unit is a fire detection control unit manufactured in conformity with the EN 54-2 and
EN 54-4 standards.
Technical features:
Multi-microprocessor system with 7" / 17,78 cm TFT display (800 x 480 with backlit), 256 colors touchscreen
with keyboard simulation to program and configure the system and the following specific functions:
End Delay, Silence Buzzer, Silence / Resound, Reset, Evacuation.
Detection LINES:
•
1 analogue loop programmable to closed or open loop for the connection of the field devices.
•
Each loop provides address for 99 detectors + 99 input and output modules with Honeywell protocol.
POWER SUPPLY:
•
Input: 100 ... 240 V AC, 50 / 60 Hz
•
Voltage 27,6 V DC / 4 A total
•
Battery charger 27,5 V DC – 0,54 A (with temperature compensation)
•
User output:
28 V DC (+ 3 % +/ - 18 %) 1 A, on board to power external loads such as loads.
I max A 1,54 A
I max B 1,62 A
I min 102,7 mA
•
Fuse 230 V AC, 3,15 A
OUTPUTS:
•
1 Supervised Sounder Output (EOL 47 KΩ or Diode)
•
1 General Alarm Output with volt-free / potential-free contacts and supervised Output (EOL 47KΩ or Diode)
•
1 General Fault Output with volt-free / potential-free contacts
•
2 Optional outputs with volt-free / potential-free contacts and supervised Output (EOL 47 KΩ or Diode)
Mechanics
The control unit mechanics is suitable for wall installations.
For cabinet sizes refer to the "MA-1000 dimensions"
•
Protection grade: IP 30
•
Operation temperature: -5 °C ... +40 °C
•
Storage temperature: -10 °C ... +50 °C
•
Weight: 2 Kg
Main Functions
•
3 passcode levels (Operator - Maintenance – Configuration)
•
4 total access levels in conformity with the EN 54 standards
•
40 zonal indicators on screen display
•
Programmable text: Point description up to 32 characters and Zone description up to 32 characters
•
2000 physical zones, 800 logical equation, 400 logical groups (stand-alone)
•
CBE Control Equations (Control-by event) for activation with logical operators (and, or etc.)
•
History Event file with the last 10.000 events in non-volatile memory
•
Real time clock
•
Line self-programming with automatic recognition of the type of the connected devices
•
Double address detection
•
Decision algorithms for the alarm and fault criteria
•
Automatic sensitivity changes, Day/Night mode
•
Contaminated detector notification
•
Programmable alarm threshold for sensors
•
Pre-defined software function programming for the various devices used
•
Walk-Test function for zones
8
M-167.1-MA1000-EN / 02.2023