Structure With Modules On Cc-Link Ie Tsn And Ethernet Devices - Mitsubishi Electric MELSEC iQ-R Series User Manual

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Structure with modules on CC-Link IE TSN and Ethernet devices

Connection with modules on CC-Link IE TSN and Ethernet devices
■Line topology
Connect Ethernet devices to the end of the network.
No.0
Class B
No.0: Master station
No.1: Local station
No.2: Remote station
(1) Ethernet device
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
■Star topology
Modules or Ethernet devices are connected in a star topology via a switching hub.
No.0
Class B
No.1
Class B
No.0: Master station
No.1: Local station
No.2: Remote station
(1) Ethernet device
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
Since cyclic data is sent to an Ethernet device when "Communication Mode" is set to "Multicast" and a local
station is used with an Ethernet device on the end side via a switching hub, communication may not be
possible depending on the type of an Ethernet device.
The communication will be enabled by configuring settings with the TSN hub so that the multicast frame (with
multicast MAC address 09:00:70:00:10:02 and 09:00:70:00:10:05) will not be transferred to the port of the
Ethernet device.
5 SYSTEM CONFIGURATION (RJ71GN11-T2)
58
5.2 Structure with CC-Link IE TSN Class B/A Devices
No.1
Class B
No.2
Class A
(1)
(1)
No.2
Class A