Operation when the protocol version 2.0 and 1.0 are combined
The following table lists the restrictions when the protocol version 2.0 and 1.0 in connected devices are combined.
Protocol version 2.0/1.0
CC-Link IE TSN Class B
device
Protocol version 2.0 only
With protocol version 1.0
Protocol version 2.0 only
With protocol version 1.0
Operation when combining versions with other products
The following describes the operation of the parameters used in the RJ71GN11-T2 when a compatible/incompatible product is
combined.
■Combination with the engineering tool
• "CC-Link IE TSN Class Setting" of each device station in the "CC-Link IE TSN Configuration" window
Engineering tool
1.080J or earlier
1.085P or later
• Magnification setting of "Low-Speed" in "Multiple Period Setting" under "Basic Settings"
Engineering tool
1.080J or earlier
1.085P or later
• "TSN HUB Setting" in "Connection Device Information" under "Basic Settings"
Engineering tool
1.080J or earlier
1.085P or later
Precautions
When the parameters of a project created with an engineering tool with version 1.080J or earlier is written by using an
engineering tool with version 1.085P or later, the module will operate with protocol version 1.0 unless the "CC-Link IE TSN
Configuration" window is opened once.
■Combination with a device station
When a CC-Link IE TSN Class A device that supports CANopen profile with the protocol version 2.0 is connected, use the
RJ71GN11-T2 with the firmware version "15" or later.
APPX
108
Appendix 1 System Configuration with CC-Link IE TSN Class B/A Devices (Protocol Version 2.0/1.0) (RJ71GN11-T2)
CC-Link IE TSN Class A
device
Protocol version 2.0 only
With protocol version 1.0
RJ71GN11-T2
Firmware version "13" or earlier
Firmware version "14" or later
Firmware version "13" or earlier
Firmware version "14" or later
RJ71GN11-T2
Firmware version "13" or earlier
Firmware version "14" or later
Firmware version "13" or earlier
Firmware version "14" or later
RJ71GN11-T2
Firmware version "13" or earlier
Firmware version "14" or later
Firmware version "13" or earlier
Firmware version "14" or later
Restrictions
Not available
A connection cannot be made if the total cyclic data size of all device stations on the CC-
Link IE TSN Class A device side at the boundary between CC-Link IE TSN Class B and
CC-Link IE TSN Class A exceeds 2K bytes.
• Up to eight CC-Link IE TSN Class B devices can be connected to each port of a master
station.
• A connection cannot be made if the total cyclic data size of all device stations on the CC-
Link IE TSN Class A device side at the boundary between CC-Link IE TSN Class B and
CC-Link IE TSN Class A exceeds 2K bytes.
Operation
The module operates with the protocol version 1.0.
The module operates with the protocol version 1.0.
The module operates with the protocol version 1.0.
The module operates with the protocol version 2.0/
1.0.
Operation
Only "16" can be set.
Only "16" can be set.
If a value other than "16" is set, a network
parameter error (error code: 2221H) occurs.
"16", "32", "64", "128" can be selected.
Operation
The setting is not available.
The setting is not available.
The module operates with the protocol version 1.0
regardless of the settings.
The module operates with the protocol version 2.0/
1.0.