Table 10 External Battery Cabinet Specifications - Emerson Liebert GXT3-5000RT230 User Manual

Table of Contents

Advertisement

Table 10
External battery cabinet specifications
Model Number
Used with UPS Model
Dimensions, W x D x H, mm (in.)
Unit (with bezel)
Shipping
Weight, kg (lb)
Shipping
Battery Parameters
Quantity x V
Battery Manufacturer, Part #
Backup Time
Environmental
Operating Temp, °C (°F)
Storage Temp, °C (°F)
Relative Humidity
Operating Elevation
Agency
Transportation
GXT3-240VBATTCE
GXT3-5000RT230
GXT3-6000RT230
430 x 574 x 130 (16.9 x 22.6 x 5.8)
530 x 745 x 407 (20.9 x 20.3 x 16.0)
Unit
43 (94.8)
54 (119)
Type
CSB HR1221W
Safety
Valve-regulated, non-spillable, lead acid
1 x 20 x 12V
See Table 11
0 to 40 (32 to 104)
see Table 8 - Operating temperature parameters
-15 to 50 (5 to 122)
0-95% non-condensing
Up to 1000m (3280.83 ft.) at 25°C (77°F)
IEC62040-1:2008 version
ISTA Procedure 1A
37
Specifications
GXT3-240RTVBATT
GXT3-10000RT230
430 x 581 x 173 (16.9 x 22.9 x 6.8)
530 x 745 x 475 (20.9 x 29.3 x 18.7)
65 (143.3)
76 (167.6)
CSB HR 1234W

Advertisement