Superlink Setting - Mitsubishi Heavy Industries SC-WBGW256 Configuration Manual

Superlink web & bacnet gateway
Hide thumbs Also See for SC-WBGW256:
Table of Contents

Advertisement

(6) You can set the Network Configuration (IP address, the subnet mask and default Gateway), Security
Configuration , login ID setting (user ID and password) to the factory default status by the following procedure.
1. Connect the DI3 and COM terminals with the harness and turn on the power.
2. Turn the power off after 5 minutes, disconnect the harness, then turn on the power again.
Be sure to remove the harness and then turn on the power again.

3 Superlink setting

In the Basic Configuration Menu screen in the Configuration Menu, click "Network Configuration".
Set the Superlink communication system setting according to the situation of the site.
SC-WBGW256 Configuration Manual(BACnet) Ver.1.0
Gateway
Harness
7
Document No. ISTZ17022 June 1, 2017