7.1.3 Air-con Cell Number (CELL No.)

The gateway performs monitoring and control by the cell number.
The cell numbers C000~C255 are assigned to the indoor units specified by the SL system number and SL
Address. Attach a cell number to the indoor unit connected to the SUPERLINK.
It is not necessary to attach a cell number to indoor units that are not connected.
Cell number C000~C255 can be freely assigned to the indoor units. Assign cell numbers to the desired
display order in the Overview Monitor screen.
Moreover, a cell number can set up the indoor unit remote control group. When two or more indoor units are
specified as a remote control group, attach the same cell number to these indoor units to define the group.
Maximum number of the indoor units that form a group is 16. In case of groups, only the indoor unit having
the smallest SL system number or SL address (SL system number being the priority) will be assigned the
"Air-con Cell Name" and "Description" explained in the following clause.

7.1.4 Air-conditioner Cell name

Assign an understandable name to a particular cell number. The length of the character string can be up to 16
characters.

7.1.5 Description

A description more detailed than the cell name can be assigned to a cell number. The length of the character
string can be up to 64 characters. Leave it blank in case recording a detailed description is not necessary.

7.1.6 Accounting Type

Choose from the following the calculating method for the indoor unit.
Type
MULTI1
MULTI2
RUN/STOP
・Select same type for same meter.
・When you select MULTI1 or MULTI2, fan mode units are out of calculation.
To calculate the fan mode units, please select RUN/STOP.

7.1.7 Indoor Unit Capacity (Capacity)

Choose the nominal capacity (Cooling capacity) of the indoor unit.
(0.0/1.5/2.0/2.2//・・・//50.0/56.0/84.0//・・・//224.0 kW)
7.1.8 Information of Indoor units to connected meter(P1~P8)
Set to check box for "v", the connected meter (P1 to P8) for each indoor unit. The meter, is possible to set
more than one meter.
7.1.9 Meter(P1~P8)
Choose the type of meter (GAS/WATT). Choose blank for not connect the meter terminals.
Choose the meter's 1 pulse per unit volume (0 - 300). The gas meter's unit is " m
"kWh".

7.1.10 Calculation interval

Choose (1 / 4 / 8 / 12 or 24 hours) for calculation interval. Run the calculation to specify hourly to starting
from 00: 00. If you choose 8 hours, it calculates at 00: 00, 08: 00, 16: 00.
Calculating Method
Calculating according to the amount of refrigerant flow.
Applicable to KX Series.
Calculating according to the thermo ON/OFF.
Applicable to KX Series.
Calculating according to the unit operating time.
Applicable to Multi-indoor unit PAC, Single PAC, PAC for equipment
(with I/F) and Superlink Adapter.
17
SC-WBGW256 Configuration Manual(BACnet) Ver.1.0
Document No. ISTZ17022 June 1, 2017