Bacnet Service Startup Configuration - Mitsubishi Heavy Industries SC-WBGW256 Configuration Manual

Superlink web & bacnet gateway
Hide thumbs Also See for SC-WBGW256:
Table of Contents

Advertisement

SC-WBGW256 Configuration Manual(BACnet) Ver.1.0
Document No. ISTZ17022 June 1, 2017

6 BACnet service Startup Configuration

BACnet configuration such as the BACnet transmission start delay can be selected.
About 1 minute later, BACnet transmission starts (Factory setting) or about 3 minute later, BACnet transmission starts
(select the check box) can be selected.
(1)
In the BACnet Configuration Menu screen in the Configuration Menu screen, click the "BACnet service Startup
Configuration".
The BACnet service Startup Configuration screen will appear as shown in Fig. 9.
(2)
To set startup delay, Select the check box and click the Set button. After confirmation, the gateway will be rebooted
automatically.
(3) After the gateway restarts, the gateway will work as the new configuration.
Fig. 9 BACnet service Startup Configuration screen
12