7 Air-con CELL Configuration

Each BACnet objects are linked to a logical unit named "Air-con Cell". The Air-con Cell configuration, that is the
relationship between the Superlink address and the Cell No., can be set by accessing the WEB Server embedded in the
gateway.
7.1

Air-conditioner Cell Configuration

At the factory, all the 256 Cells from Cell000 to Cell255 have been set as the default setting. The default setting
should be changed so as to match the actual Superlink address allocation at the site.
(1) To get the Air-conditioner Cell Configuration, click the "Air-conditioner Cell Configuration" in the Basic
Configuration Menu screen in the Configuration Menu screen. The Air-conditioner Cell Configuration screen will
appear as shown in Fig. 10.
(2) Using the pull-down menu, set a Cell No. for which each Air-conditioner belongs. To see all the rows, use the
scroll bar at the right side.
(3) Click the "Set" button to activate the new setting.
7.1.1 SL System Number (SL Sys No)
Two SL system numbers for the gateway are written as S1 and S2.

7.1.2 Superlink Address (SL Address)

The SL Address of an indoor unit is written as U000~U127.
SL system number and SL Address are shown in ascending order. For Prev. SL, use U000~U047.
Fig. 10 Air-conditioner Cell Configuration screen
13
SC-WBGW256 Configuration Manual(BACnet) Ver.1.0
Document No. ISTZ17022 June 1, 2017