7.2 PACinfo256.csv (PACinfo256.xml) File

PACinfo256.csv and PACinfo256.xml are exclusive to the gateway.
The setting information in the Air-con Cell Configuration screen can be downloaded from the Air-conditioner Cell
Configuration File Upload/Download screen and the file can be saved to the computer. This file is called
PACinfo256.csv or PACinfo256.xml. Aside from being a backup file, PACinfo256.csv or PACinfo256.xml can also be
edited using Notepad or EXCEL applications. Edited PACinfo256.csv or PACinfo256.xml can be uploaded from the
Air-conditioner Cell Configuration File screen and can be set as the cell setting.
When opening PACinfo256.csv file with a text editor, it will be displayed as follows.
lines
CELL_NO,PLACE,PLACE_SHORT,SL_LINE,SL_ADDRESS,KAKIN_TYPE,ABILITY,P1,T1,C1,P2,T2,C2,P3,T3,C3,P4,T4,C4,P5,T5,C5
1
,P6,T6,C6,P7,T7,C7,P8,T8,C8,INTERVAL
C000,This room is Cell 000.,Room 000,S1,U000,RUN/STOP,10,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,1
2
C001,This room is Cell 001.,Room 001,S1,U001,RUN/STOP,20,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,1
3
C001,This room is Cell 001.,Room 001,S1,U002,RUN/STOP,10,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,1
4
C001,This room is Cell 001.,Room 001,S1,U003,RUN/STOP,10,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,1
5
C001,This room is Cell 001.,Room 001,S1,U004,RUN/STOP,0,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,OFF,,,1
6
The CSV file is stored where a comma separates each item. The first line expresses the title of each item to show
the order of the items (Air-con Cell Number(
, SL System No.(
SHORT)
Information of Indoor units to connected meter(P1), P1 Type(T1), P1 Pulse Constant(C1),・・・,P8 Type(T8), P8
Pulse Constant(C8), Calculation .Interval(INTERVAL)). The second and succeeding lines show the data from the
Air-conditioner Cell Configuration File screen. Since each item is separated by commas, a comma cannot be
inputted into the contents of each item. If a comma is inputted, the gateway will not be able to recognize it
correctly.
Attention:
Do not use ", & < > " '" for each input item. If you enter these characters and upload the file, the screen may not
be displayed correctly. In this case, turn off the power of this gateway, turn on the power again, and upload the file
without ", & < > " '".
Fig. 11 PACinfo256.csv file opened using text editor (example)
CELL_NO)
, SL Address(
SL_LINE)
SL_ADDRESS)
SC-WBGW256 Configuration Manual(BACnet) Ver.1.0
, Description(PLACE), Air-conditioner Cell Name(
, Accounting Type(
18
Document No. ISTZ17022 June 1, 2017
, Capacity(
KAKIN_TYPE)
_
PLACE
,
ABILITY)