Series And Parallel Operation; Series Operation - TDK-Lambda GENESYS 15KW User Manual

Programmable dc power supplies
Hide thumbs Also See for GENESYS 15KW:
Table of Contents

Advertisement

6. SERIES AND PARALLEL OPERATION

Users may connect the outputs of Genesys™ Power Supplies together to produce:
▬ Voltages greater than any one supply rating (series connection).
▬ Plus and minus polarity (series connection).
▬ More current than any one supply rating (parallel connection).
In addition to connecting the outputs together, Remote Analog control connections are
used to ensure the supplies are properly sharing the total voltage or current. Remote
Digital programming through the RS-232/RS-485, LAN, IEMD or USB is allowed for all
power supplies.
Consult your local TDK-Lambda Sales/Technical Support representative to
When a Power Supply is set to Remote Analog control then the
corresponding voltage or current encoder (and their PREView settings) will
Although the front panel seems like it can be used to adjust the Output
settings, it is the Remote Analog control lines that actually set the

6.1. Series Operation

Power supplies of the SAME MODEL can be connected in series to obtain increased
Output voltage. Split connection of the power supplies gives positive and negative Output
voltage.
Do not connect power supplies from different manufacturers in
Use only the same models for series or parallel connection.
6.1.1. Series Connection for Increased Output Voltage
In this mode, two units are connected so that their Output voltages are summed
(Series Operation). Set the Output current limit of each Power Supply to the
maximum that the load can handle without damage. It is recommended that diodes
be connected in parallel with each unit Output to prevent reverse voltage during the
startup sequence or in case one unit shuts down. Each diode should be rated for at
least the Power Supply rated Output voltage and Output current. Refer to Fig.6-1 and
6-2 for Series Operation with Local and Remote sensing.
NOTE
discuss your Series or Parallel application in detail.
NOTE
not be effective.
programming limits.
CAUTION
series or in parallel.
57
83532002 Rev H

Advertisement

Table of Contents
loading

This manual is also suitable for:

Genesys 10kw

Table of Contents