How To Enable Bluetooth On The Operating Panel; How To Disable Bluetooth On The Operating Panel; Testing The Product; Product Introduction - Grundfos CU 242 Installation And Operating Instructions Manual

Dual pump unit
Table of Contents

Advertisement

Related information
6.1 Setting the application type with Grundfos GO Remote
6.26 Starting the startup wizard with the operating panel

3.4 How to enable Bluetooth on the operating panel

If the Bluetooth signal on the operating panel has been disabled for
some reason, you are not able to connect with Grundfos GO
Remote. You must enable Bluetooth first.
1. Press and hold the connect button on the operating panel for 15
seconds. Wait for the blue LED to light up.
2. Press the Bluetooth CONNECT button on Grundfos GO
Remote.
3. Press the connect button on the operating panel. The blue LED
above the connect button is flashing blue until your device is
connected.
Grundfos GO Remote is now loading the data for the product.
Related information
3.1 Connecting to Grundfos GO Remote

3.5 How to disable Bluetooth on the operating panel

In some installation areas, it is not allowed to have a Bluetooth
signal enabled during operation. After installation, the Bluetooth
signal must be disabled manually.
1. Press and hold the connect button on the operating panel for 15
seconds. Wait for the blue LED to switch off.
Grundfos GO Remote is no longer connected to the product.
Related information
3.1 Connecting to Grundfos GO Remote

3.6 Testing the product

When you have made all the electrical installations and completed
the startup wizard, you can test the system.
For dewatering applications:
Ensure the pit is filled with water and check that the pump starts
automatically at the defined level.
If possible, test the dry-running function by starting the pump
manually and wait while the pit with the pump is emptied. Check
that the control unit indicates an alarm and stops the pump
when the defined level is reached.
For filling applications:
Start by draining the tank to be filled. When the tank is empty
and the start level is reached, the pump must start. When the
tank is full and the stop level is reached, the pump must stop.
Test the high-level function by stopping the pump manually and
continue to fill the tank without the pump with water. Check that
the control unit indicates an alarm when the defined level is
reached.
Test the dry-running function by starting the pump manually and
wait while the tank with the pump is emptied. Check that the
control unit indicates an alarm and stops the pump when the
defined level is reached. If the pump is placed in a well, this test
may not be possible since the pump cannot empty the well.
Alternatively, pull the dry-run level switch up to simulate a dry-
run situation. The same can be done with a pressure level
sensor.

4. Product introduction

4.1 Product description

The level-control unit switches the pump on and off according to the
liquid level measured by float switches or a pressure sensor. When
the start level is reached, the pump starts, and when the liquid level
has been lowered to the stop level, the pump is stopped by the
control unit. An alarm is indicated in case of for example high-water
level in the tank or sensor failure.
Basic settings are configured via the operating panel and advanced
settings are configured with Grundfos GO Remote. Furthermore,
you can read important operating parameters with Grundfos GO
Remote.
8

4.2 Intended use

The product is designed to control one or two pumps.
The product can be configured for the following two purposes:
dewatering in groundwater supply
filling a tank.
The product can be used for the following applications:
groundwater supply
irrigation systems
small waterworks
network pumping stations
main pumping stations
commercial buildings
municipal systems.
The product must not be exposed to strong solvents or oil-
containing liquids.

4.3 Features

The control unit features among others the following functions:
support of up to two pumps
manual and automatic control of the pump
Bluetooth pairing with Grundfos GO Remote
operating indication, such as power on and pump running
alarm and warning indication, such as power phase missing and
high-water level
motor and phase failure protection
setting of stop delays matching the actual operating conditions
automatic alternation of pumps.

4.4 Application types

You can choose between two application types:
Dewatering
Fill.
You can set the application type with Grundfos GO Remote.
Dewatering
Pos.
Description
1
High level
2
Start level P2: start level for pump 2
3
Start level P1: start level for pump 1
4
Stop level
5
Dry-running level
The pump starts to empty the tank or well when Start level P1 is
reached.
A second pump starts when the liquid level reaches Start level P2.
The pump stops when the liquid level is lowered to Stop level.
If the inflow of liquid exceeds the capacity of the installed pump, the
level in the tank or well starts to rise. Eventually, the High level
sensor registers a high liquid level in the tank or well. If set, the
1
2
3
4
5

Advertisement

Table of Contents
loading