Declaration of Conformity We Grundfos declare under our sole responsibility that the product CU 300, to which this declaration relates, is in conformity with the Council Directives on the approximation of the laws of the EC Member States relating to —...
- 0 to 10 bar 7.5.4 Potentiometer SPP 1 Description Settings Function 7.6.1 Required R100 settings Positioning the pressure sensor CU 300 connected to water meter 30 System sizing Description Installation Installation Location Location Mounting the CU 300 Mounting the CU 300...
Page 4
12.4.9 Button on CU 300 CU 300 connected to RS-232, 12.4.10 Number RS-485 Technical data 10.1 Description Disposal 10.2 CU 300 connected to a PC directly 10.3 Installation 10.4 Location 10.5 Mounting the CU 300 10.6 Electrical connection 10.6.1 Mains supply 10.6.2 Pump supply...
1.2 On/Off button Before beginning installation procedures, these installation and operating instruc- By means of the On/Off button on the CU 300, it is tions should be studied carefully. The in- possible to stallation and operation should also be in •...
Fig. 2 shows an example of an installation with the CU 300 as an alarm unit. Fig. 2 The CU 300 is supplied with a set of gaskets for the Pg screwed connections. The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
2.5 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
If the pump power input falls below the dry-running dry-running protection function, the following R100 power limit set in the R100 display 12.4.6 Dry-run- settings must be made: ning stop, the pump will stop and the CU 300 will indicate the dry-running alarm. Display R100 setting 2.6.1 Function...
Fig. 6 For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis- play has a number which refers to the section in which it is described in detail.
The pressure is registered by means of the pressure to 0.5 bar below the pressure setting. sensor, which transmits a signal to the CU 300. The The pump will run until the pressure is 0.5 bar above CU 300 adjusts the pump performance accordingly the pressure set.
Fig. 9 3.3 Positioning the pressure sensor Pressure loss often causes inconvenience to the Pressure user. The CU 300 keeps the pressure constant in the Flow detection place where the pressure sensor is positioned, see fig. 11. Fig. 11 Shower...
Fig. 12 104.5 104.5 The CU 300 is supplied with a set of gaskets for the Pg screwed connections. The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
3.8 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
For a detailed description of the R100 displays, see • l/pulse to “–” (not active). section 12. CU 300 with R100. Each individual dis- play has a number which refers to the section in which it is described in detail.
A = Required pressure 4.3 Positioning the pressure sensor Pressure loss often causes inconvenience to the Pos. Description user. The CU 300 keeps the pressure constant in the place where the pressure sensor is positioned, see CU 300 fig. 16. Diaphragm tank Fig.
Fig. 17 104.5 104.5 The CU 300 is supplied with a set of gaskets for the Pg screwed connections. The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
4.8 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
• l/pulse to “–” (not active). For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis- play has a number which refers to the section in Set the desired head (m).
0.5 bar. If the consumption exceeds the quantity the pump connected to the CU 300 (master) is able to de- liver, the pressure in the diaphragm tank will fall. The pump connected to the CU 300 (slave) will be started in the two following situations: 1.
Fig. 21 104.5 104.5 The CU 300 is supplied with a set of gaskets for the Pg screwed connections. The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
5.8 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
5.8.5 Flow switch and pressure sensor 12.3.10 Digital in- Connect the flow switch and the pressure sensor to the CU 300 (A = master) as illustrated in fig. 22. • Type to “Start” and Flow switch: • l/pulse to “–” (not active).
6.1 General automatically “not active”. These settings are made in the R100 displays The CU 300 can be used in systems with 1 to 3 sen- 12.3.1 to 12.3.9. sors connected. Fig. 23 shows an example of an installation incorpo- 6.2 Sensor functioning...
• Filling means that the pump must start at a given The CU 300 is supplied with a set of gaskets for the minimum water level and stop at a given maxi- Pg screwed connections. mum water level, see fig. 26.
6.6 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
For a detailed description of the R100 displays, see Set the desired stop 12.3.9 Stop type section 12. CU 300 with R100. Each individual dis- type. play has a number which refers to the section in Example: which it is described in detail.
Fig. 30 rating a potentiometer. Fig. 29 104.5 104.5 The CU 300 is supplied with a set of gaskets for the Pg screwed connections. Pos. Description The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and CU 300 cable relief.
7.5 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
For a detailed description of the R100 displays, see leads of the pump. Each terminal can be connected section 12. CU 300 with R100. Each individual dis- to any of the two leads. play has a number which refers to the section in Connect the PE terminal to the green/yellow earth which it is described in detail.
Fig. 33 incorporating a water meter. Fig. 32 104.5 104.5 The CU 300 is supplied with a set of gaskets for the Pg screwed connections. The gaskets are to be used for the connection of Pos. Description cables/wires to ensure tight connections (IP 55) and CU 300 cable relief.
8.5 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis- play has a number which refers to the section in which it is described in detail.
The CU 300 controls the pump speed and conse- quently adjusts the pump performance to the bore- hole yield. The CU 300 is supplied with a set of gaskets for the 1. When the water level is much higher than the de- Pg screwed connections.
9.6 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
For a detailed description of the R100 displays, see leads of the pump. Each terminal can be connected section 12. CU 300 with R100. Each individual dis- to any of the two leads. play has a number which refers to the section in Connect the PE terminal to the green/yellow earth which it is described in detail.
• connection to the Grundfos G100 gateway for Fig. 39 communication over long distances, e.g. via radio. 10.2 CU 300 connected to a PC directly Fig. 38 shows an example of an installation which is connected to a PC directly via the RS-232 input.
104.5 Fig. 40 G 100 GATEWAY The CU 300 is supplied with a set of gaskets for the Pg screwed connections. The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
10.6 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for Never make any connections in the the electricity supply on which it will be used. CU 300 unit unless the electricity supply has been switched off.
The RS-485 input, terminals A, Y (GND) and B, is for external bus communication. The PC Tool CU 300 is Windows95/NT-based soft- The communication is effected according to the ware, see the PC Tool CU 300 opening display in fig. Grundfos bus protocol, GENIbus, and is two-way communication. Fig. 43 The CU 300 can communicate with a PC with the PC Tool CU 300 installed.
11. Alarm functions Fig. 45 The alarm functions indicated by the eight red indica- tor lights on the CU 300 are described in the follow- No contact ing sections. Overvoltage 11.1 No contact Undervoltage The connection and/or communication between the Dry running CU 300 and the motor is not established.
Restarting: In fig. 48, the “Speed reduction” alarm was caused by undervoltage. When the supply voltage lies within the voltage range of the motor, the motor will restart automati- Fig. 48 cally. 11.4 Dry running No contact The purpose of the dry-running protection is to pro- Overvoltage tect the pump in case of insufficient water flow.
Fig. 49 Restarting: After 5 minutes (factory setting), or the period set by means of the R100 display 12.4.3 Automatic restart, No contact the motor will restart automatically. Overvoltage 11.8 Sensor alarm Undervoltage This alarm means that: Dry running • a connected sensor has detected that an alarm Speed reduction limit has been exceeded or Overtemperature...
The remote control R100 is used for wireless com- munication with the CU 300. The R100 communi- cates via infra-red light. During communication, there must be visual contact between the CU 300 and the R100, see fig. 52. Fig. 52...
Page 46
= 680 W. • Motor type 1.1 to 1.73 kW, dry-running stop = 800 W. 12.4.7 Dry-running protection Active Motor 12.4.8 Maximum speed 10,700 min Motor 12.4.9 Button on CU 300 Active CU 300 12.4.10 Number – CU 300 and motor...
12.1 Menu OPERATION Select one of the following operating modes: • Max. The OPERATION menu for the CU 300 offers the Pump operation is set to maximum speed, irre- possibility of setting and reading operating parame- spective of setpoint. The maximum speed is set in ters.
The operating mode was selected from one of the number. following: The sensor 2 signal has fallen • CU 300 (On/Off button on the CU 300). outside the measuring range • R100. set. Alarm, sensor 2 •...
The value of number of starts is accumulated from the pump’s birth and it cannot be reset. The value is stored in the motor electronics, and it is kept even if the CU 300 is replaced. 12.2.7 Sensor 1 and sensor 2 The actual speed stated in min (rpm).
12.3.3 Warning, sensor 1 12.3 Menu LIMITS The LIMITS menu for the CU 300 offers the possibil- ity of setting limit values for pump/motor and sensor operation. It is possible to set both stop, warning and alarm limits in this menu.
12.3.5 Sensor 2 Set the maximum and minimum warning limits of sensor 2. Setting range/unit: • Maximum value: “–” (not active), possible settings according to the setting in display 12.3.5 Sensor 2. • Minimum value: “–” (not active), possible settings according to the setting in display 12.3.5 Sensor 2.
Usage: This function can be used e.g. if the pumped liquid contains a relatively high level of ochre. 12.4 Menu INSTALLATION The INSTALLATION menu for the CU 300 offers the possibility of configuring the CU 300, pump/motor and sensors. Factory settings are marked in bold-faced type Stop: under each individual display.
If an SPP 1 potentiometer is connected, the internal in display 12.1.1 Setpoint (e.g. 10,700 min ) or voltage supply of the CU 300 is used to generate the controlled by means of a signal connected to sen- signal. sor input 2.
See section 2.8 Description of the dewatering func- tion. Operating indication: The dry-running alarm indication on the CU 300 is automatically disabled, when this display setting is made. When the setting “–” is selected, the dewatering function is disabled, and the dry-running alarm indi- The following settings are available: cation can be activated again.
(not active) is no longer available. In connection with bus communication, a number must be allocated to the CU 300 and the pump. If the CU 300 and the pump do not have the same number, the alarm “No contact” will be indicated.
0-24 VDC, 10 kΩ (via internal voltage supply). Maximum 95%. Screened cable is recommended. Materials Maximum cable length: 100 m. The CU 300 box is made of black PPO. Voltage signal: 0-10 VDC/2-10 VDC, R = 11 kΩ. EMC (Electromagnetic compatibility) Tolerance: ±3% at maximum voltage signal.
2. In case such waste collection service does not exist or cannot handle the materials used in the product, please deliver the product or any haz- ardous materials from it to your nearest Grundfos company or service workshop. Subject to alterations.
Page 58
GRUNDFOS Gulf Distribution Co. Ltd. Poland P.O. Box 16768 Indonesia 22 Floor, Xin Hua Lian Building GRUNDFOS Pompy Sp. z o.o. Jebel Ali Free Zone PT GRUNDFOS Pompa 755-775 Huai Hai Rd, (M) ul. Klonowa 23 Dubai Jl. Rawa Sumur III, Blok III/CC-1 Shanghai 200020 Baranowo k.
Page 59
Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96427972 1204 Repl. 96427972 0802 www.grundfos.com...
Need help?
Do you have a question about the CU 300 and is the answer not in the manual?
Questions and answers