Connection dia-
The ripple control signal receiver and the I/Os terminal of the inverter can be
gram - 2 relay
connected to one another in accordance with the connection diagram.
If the distance between the inverter and the ripple control signal receiver ex-
ceeds 10 m, at least a CAT 5 cable is recommended and the shield must be con-
nected at one end to the push-in terminal of the data communication area
(SHIELD).
(1)
(2)
Use the preconfigured file for 2-relay mode:
1
2
3
The settings for 2-relay mode are stored.
134
(1)
Relais 1
Relais 2
Relais 1
Relais 2
Active Power
0
0
100 %
1
0
60 %
0
1
30 %
1
1
0 %
Ripple control signal receiver with 2 relays, for effective power limiting.
I/Os of the data communication area.
Download the file (.fpc)
Upload the file (.fpc) in the
port"
button.
Click on the
"Save"
button.