Closing and commissioning the inverter

Closing the in-
NOTE!
verter's connec-
The housing cover is fitted with a lock for safety reasons, which allows the hous-
tion area/hous-
ing cover on the inverter to be pivoted only when the DC disconnector is
ing cover, and
commissioning
switched off.
1
2
Starting the in-
When starting the inverter for the first time, various setup settings must be con-
verter for the
figured.
first time
If the setup process is cancelled before the process is complete, any data that
has been input up to this point is lost and the start screen with the installation
wizard is shown again. If the process is interrupted, such as in the event of a
power outage, the data is saved. Commissioning may be continued from the point
at which the process was interrupted once the power supply has been restored. If
the setup was interrupted, the inverter feeds energy into the grid at maximum
500 W and the operating status LED flashes yellow.
Only clip and pivot the housing cover onto the inverter when the DC discon-
nector is switched off.
Do not use excessive force to clip in and pivot the housing cover.
Place the cover on the connection
area. Tighten the five screws by rotat-
ing them 180° to the right in the indic-
ated order using a screwdriver (TX20).
Clip the housing cover in at the top of
the inverter.
Press on the lower part of the housing
cover and tighten the two screws 180°
to the right using a Torx screwdriver
(TX20).
Turn the DC disconnector to the "On"
switch position. Switch on the auto-
matic circuit breaker. For systems with
a battery, observe the switch-on se-
quence as per chapter
Suitable batter-
ies
on page 26.
IMPORTANT! Open WLAN Access
Point with the optical sensor, see
Button functions and LED
chapter
status indicator
on page
35