Placing The Heating Boiler Back In Service After A Prolonged Shutdown; Spark Monitor (Ac Current Transducer) - Watts Aerco BENCHMARK 750 User Manual

Gas-fired boilers
Hide thumbs Also See for Aerco BENCHMARK 750:
Table of Contents

Advertisement

Benchmark 750 – 1000 Boiler User Manual - INTERNATIONAL
7.11 PLACING THE HEATING BOILER BACK IN SERVICE AFTER A PROLONGED
SHUTDOWN
After a prolonged shutdown (one year or more), the following procedures must be followed:
Placing Heating Boiler in Service After Long Shutdown
1.
Review installation requirements included in Chapter 2.
2.
Inspect all piping and connections to the unit.
3.
Inspect exhaust vent and air inlet duct work (if applicable).
4.
Perform initial startup per Chapter 4.
5.
Perform safety device testing and scheduled maintenance procedures per Chapters 6
and 7 of this manual.

7.12 SPARK MONITOR (AC CURRENT TRANSDUCER)

The spark monitor
(P/N 61034)
transformer and igniter-injector. Wire# 140, connected to the ignition transformer (see Figure 7-
11), passes through the monitor's orifice. If an adequate AC current is not detected in the wire
during ignition, the unit automatically shuts down. The monitor's wires are connected to the
board's Spark Signal terminals (see section 2.10.4).
Spark
Monitor
To I/O
Tab
Board
Figure 7-11: Spark Detector Sensor (AC Current Transducer) P/N 61034
If the spark monitor needs to be replaced, open the monitor's orifice by pulling on the tab at
the side, remove Wire# 140, disconnect the monitor's wires are from the I/O board, r e m o v e
the old monitor from its position, i n s t a l l a new monitor in its place, r o u t e wire# 140
through the new sensor orifice, and connect the wires to the I/O board's Spark Signal
terminals, red wire to the positive (+) terminal and black to negative (-).
Page 98 of 170
11/03/2016
CHAPTER 7 – MAINTENANCE
evaluates the strength of the current between the ignition
Wire 140
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Ignition
Transformer
I/O
Wire 140
OMM-0119_0A