2.6 PRESSURE RELIEF VALVE INSTALLATION

Pressure relief valves are not required for low pressure applications, but
we recommend that they be installed as a safety measure to avoid the
build-up of pressure inside the device (although this rarely occurs).
An ASME Pressure Relief Valve rated 30 PSI (207 kPa) is supplied with each Benchmark
Boiler.
The relief valve is installed on the hot water outlet of the boiler as shown in Figure 2-4. A
suitable pipe joint compound should be used on the threaded connections. Any excess should
be wiped off to avoid getting any joint compound into the valve body. The relief valve must be
piped to within 12 inches (30.5 cm) of the floor to prevent injury in the event of a discharge.
No valves, restrictions, or other blockages are allowed in the discharge line. In multiple unit
installations the discharge lines must NOT be manifolded together. Each must be individually
run to a suitable discharge location.
PRESSURE
RELIEF VALVE
3" HOT BOILER
WATER OUTLET
See Diagram 1 in Appendix I for an example of a low-pressure piping scheme.
Page 18 of 170
11/03/2016
CHAPTER 2 – INSTALLATION
NOTE
Figure 2-4: P&T Relief Valve Location
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
INSTALL TRIDICATOR
GAUGE HERE
(P/N 123675-TAB)
OMM-0119_0A
GF-130-I

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aerco benchmark 1000Bmk 750Bmk 1000

Table of Contents