Installation Manual
3. Press any button on the VPU to switch On the unit.
4. Using the UP/DOWN scroll buttons, select an address (
to confirm the selection.
Note:
Two hundred and forty addresses are available. Address entry errors can be corrected by simply
readdressing the device (deletion not required).
5. Disconnect the VPU100 wires and reconnect the module to the Loop
Apollo devices supported by the control panel
Note:
Not all the devices accepted by this control panel are IMQ-SISTEMI DI SICUREZZA approved,
refer to the instructions leaflet of each device for details.
Apollo devices are not equipped with built-in loop isolators (that is, unless otherwise specified).
Therefore, you must install loop isolators in such way as to avoid the loss of devices in the event of
short-circuit.
B.7
Devices
B.7.1 Detectors: XP95 series
Note:
XP95 series detectors are especially designed to operate with a sensibility of 55 (sensibility at
default). Sensibility adjustment should be made only when absolutely essential, as any change
may lead to delays in loop response time.
Model
55000-885
XP95 Multisensor Detector
55000-600
XP95 Optical Smoke detector
55000-500
XP95 Ionization Smoke Detector
55000-400
XP95 Heat detector - standard temperature
55000-401
XP95 Heat detector - High temperature
55000-640
XP95 I.S. Smoke detector
55000-440
XP95 I.S.Heat detector
55000-540
XP95 I.S.Ionization Smoke detector
B.7.2 Detectors: Discovery series
Model
58000-600
Discovery Optical Smoke detector
58000-400
Discovery Heat detector
58000-700
Discovery Multisensor detector
58000-300
Discovery Carbon Monoxide detector
58000-500
Discovery Ionization Smoke detector
Apollo devices supported by the control panel
Name
Name
) then press the WRITE button (top left)
1-240
Description
Fire Smoke / Heat detector
Optical Smoke detector
Ionization Smoke Detector
Heat detector - standard temperature
Heat detector - High temperature
Intrinsic security Smoke detector
Intrinsic security Heat detector
Intrinsic security Ionization Smoke detector
Description
Optical Smoke detector
Heat detector
Optical Smoke detector + Heat detector
Carbon Monoxide detector
Ionization Smoke Detector
55
Need help?
Do you have a question about the SmartLoop and is the answer not in the manual?
Questions and answers