Table 7 - Smv Analog Output Selection - Honeywell SmartLine Multivariable SMV800 Series User Manual

Hart/de option
Hide thumbs Also See for SmartLine Multivariable SMV800 Series:
Table of Contents

Advertisement

PV1 (DP) w/SV1 (M.B.Temp)
PV1 (DP) w/SV1 & PV2 (SP)
PV1 (DP) w/SV1 - PV3 (TEMP)
PV1 (DP) w/SV1 - PV4 (FLOW) Differential Pressure (PV1), Static Pressure* (PV2) and
* Static pressure may be absolute or gauge pressure, depending on the SMV model type. (For models SMA810
and SMA845, PV2 measures absolute pressure. For model SMG870, PV2 measures gauge pressure.)
ATTENTION
To digitally integrate the SMV800 transmitter with our TPS/TDC control systems, you must have an
STIMV IOP module in your Process Manager, Advanced Process Manager, or High Performance
Process Manager. You cannot integrate the SMV800 with a control system using an STDC card or an
STI IOP module for the Smart Transmitter interface.
Contact your Honeywell representative for information about possibly upgrading an existing STI IOP
to an STIMV IOP.
Analog Output Selection
The Analog Output Selection field should contain the PV type that will represent the transmitter's
output when the transmitter is in its analog mode.
Select the PV you want to see as the SMV output from the choices in
Determine which PV is desired as SMV
PV1 – Delta P (Differential Pressure)
PV2 – Static (Absolute or Gauge Pressure)
PV3 – Proc Temp (Process Temperature)
PV4 – Calculated (Calculated Flow Rate)
d Factory setting. * Static pressure may be absolute or gauge pressure, depending on the SMV model type. (For
models SMA810 and SMA845, PV2 measure absolute pressure. For model SMG870, PV2 measures gauge
pressure.)
A transmitter output can represent only one process variable when it is operating in its analog mode.
You can select which one of the four PVs is to represent the output.
Page 24
Differential Pressure (PV1) measurement with the
Secondary Variable (SV1).
Differential Pressure (PV1) and Static Pressure* (PV2)
measurements with the Secondary Variable (SV1).
Differential Pressure (PV1), Static Pressure* (PV2) and
Process Temperature (PV3) measurements with the
Secondary Variable (SV1).
Process Temperature (PV3) measurements and the
Calculated flow rate value (PV4) with the Secondary
variable (SV1).

Table 7 - SMV Analog Output Selection

Output . . .
SMV800 Series HART/DE Option User's Manual
Table 7.
Then Select...
PV1 (DP)
PV2 (SP)*
PV3 (Temp)
d
PV4 (Flow)
Revision 6.0