8.8

Analog Input Module

The Analog Input Module is a generic unit interfacing with LONWORKS™ systems, that
use a free topology wiring scheme supporting star, loop, and/or bus wiring.
The Analog Input Module contains two isolated groups of each two analog input channels,
for processing ± 0-10 VDC or ± 0-25 mA current signals. The analog inputs can be logically
connected via a network to different input/output modules and data visualization software.
For each channel the module offers two user-settable alarm levels and input scaling.
All states are indicated by LEDs. The module provides one dedicated power loss relay with
SPST contact for activation of external alarm devices.
Network configuration data is customer specific and is programmed into nonvolatile
memory.
Technical Specifications
Power Requirements
voltage
consumption
Network
data transmission
wiring topologies
Wiring
Analog Inputs
channels
signal range
resolution
Status Indication
Relay Output
contact
max. ratings
Physical Dimensions
size
weight
Mounting
Housing Protection Class
RFI / EMC
Operating Conditions
temperature
humidity
Part Number
Satellite XT FTT Versions
Reference Information - Section 8
12 ... 24 VDC
typically 2 W
Standardized LonTalk™ protocol
78 kBit per second
free, e.g. Bus, Star, Loop, or mixed
4-wire shielded cable 2x2x1.0 mm 2 / 17 AWG
2 isolated groups of each 2 inputs
with common signal ground
± 0 - 10 VDC or ± 0 - 25 mA
14-bit, 10 samples per second
8 red input state LEDs
1 green status LED
1 yellow service LED
1 x SPST (single-pole-single-throw)
250 VAC / 30 VDC, 8 A
45 x 80 x 105 mm
1.8" x 3.1" x 4.1"
200 g
7 oz
DIN rail
IP 20
EN 55022
EN 61000-6-2
Ch 1
Ch 2
0 °C ... +40 °C
+32 °F ... +104 °F
Ch 3
20 ... 90 % r.h.
9660-0330
Ch 4
Power Requirements: 12 ... 24 VDC, typ. 2 W
Input Voltage Range: ± 0 ... 10 VDC
Input Current Range: ± 0 ... 25 mADC
Relay Ratings:
(W x H x D)
(W x H x D)
Power
Power
Loss
U+
Com–
I+
C
P+
1
2
3
4
5
not
U+
Com–
I+
used
P+
7
8
9
10
11
Network
not
U+
Com–
I+
N+
used
13
14
15
16
17
U+
Com–
I+
NO
N+
19
20
21
22
23
250 VAC / 30 VDC, 8 A
AIM
P–
6
P–
12
N–
18
N–
24