De Calibration For St 700 Standard Transmitter; Overview; Calibration Recommendations; Test Equipment Required For Calibration - Honeywell ST 700 User Manual

Smartline series
Hide thumbs Also See for ST 700:
Table of Contents

Advertisement

7 DE Calibration for ST 700 Standard Transmitter

7.1 Overview

The ST700 Standard SmartLine Pressure Transmitter does not require periodic calibration to maintain
accuracy. Typically, calibration of a process-connected Transmitter may degrade, rather than augment
its capability. For this reason, it is recommended that a Transmitter be removed from service before
calibration. Moreover, calibration will be accomplished in a controlled, laboratory-type environment,
using certified precision equipment.

7.2 Calibration Recommendations

If the Transmitter is digitally integrated with a Honeywell Total Plant Solution (TPS) system, you can
initiate range calibration and associated reset functions through displays at the Universal Station,
Global User Station (GUS), and Allen-Bradley Programmable Logic Controllers (PLCs). However, a
range calibration using the MC Toolkit with the Transmitter removed from service is recommended.
Calibration with the Transmitter removed from service needs to be accomplished in a controlled
environment. Details for performing a calibration reset through the Universal Station are provided in
the PM/APM SmartLine Transmitter Integration Manual, PM12-410, which is part of the TDC 3000
system book set.

7.3 Test Equipment Required for Calibration

Depending upon the type of calibration you choose, you may need any of the following test
equipment to accurately calibrate the transmitter:
Digital Voltmeter or millimeter with 0.01% accuracy or better
Honeywell MC Toolkit: Use the MC Toolkit application to calibrate the ST 700 DE model
and the FDC application to calibrate the ST 700 HART model.
Calibration-standard input source with a 0.01% accuracy
250ohm resistor with 0.01% tolerance or better.

7.4 Analog Output Signal Calibration

The Transmitter analog output can be calibrated at its zero (0) and100% levels using a constant-
current source mode. The Transmitter does not have to be removed from service for the analog output
signal calibration procedure.