Technical Specifications; Etu600 Commissioning - Siemens SENTRON 3WA1 Manual

Table of Contents

Advertisement

2.5.7

Technical specifications

Design of the power supply
DC power supply unit
Rated supply voltage U
Operating range
Power consumption
Maximum current consumption
Starting current / maximum (for 5 ms)
Overvoltage category
Integrated short-circuit protection
Protected against polarity reversal
2.5.8

ETU600 commissioning

When commissioning the ETU600 electronic trip unit, device parameters must be set in
addition to the parameters for the protection functions. The setting can be made on the
ETU600 display, menu item 5.0 "Device configuration".
The following description refers to the menu items in the display of the ETU600.
Alternatively, the settings can also be made using the SENTRON powerconfig
configuration software via Bluetooth or communication.
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
s
2.5 Electronic trip unit ETU600
DC power supply unit
IEC 61558 SELV/PELV
24 V DC
U
± 20%
s
2.9 W
0.12 A
0.35 A
CAT I
Description
123