Derating 3Wa12 - Siemens SENTRON 3WA1 Manual

Table of Contents

Advertisement

Integration in power distribution equipment
7.3 Derating in the power distribution equipment
7.3.3

Derating 3WA12

The following tables show the derating for size 2, installed in a control panel.
Fixed-mounted, IP31/IP41 - ventilated
Rated
Conductor cross-
current
section
2000 A
3 x 50 mm x 10 mm 1
2500 A
2 x 100 mm x
10 mm
3200 A
3 x 100 mm x
10 mm
4000 A
4 x 120 mm x
10 mm
Note
When the 3WA12 circuit breaker is used in the range I
considered.
Fixed-mounted, IP55
Rated
Conductor cross-
current
section
2000 A
3 x 50 mm x 10 mm 1
2500 A
2 x 100 mm x
10 mm
3200 A
3 x 100 mm x
10 mm
4000 A
4 x 120 mm x
10 mm
Note
When the 3WA12 circuit breaker is used in the range I
considered.
522
Control panel dimensions H x W x D [mm]: 2200 x 800 x 800
Number
of 3WAs
20 °C
2000 A
2
2000 A
1
2500 A
2
2500 A
1
3200 A
2
3200 A
1
4000 A
Control panel dimensions H x W x D [mm]: 2200 x 800 x 800
Number
of 3WAs
20 °C
1910 A
2
1830 A
1
2300 A
2
2290 A
1
2900 A
2
2540 A
1
3720 A
Max. operational current at ambient temperature
25 °C
30 °C
35 °C
2000 A
2000 A
2000 A
2000 A
2000 A
2000 A
2500 A
2500 A
2500 A
2500 A
2480 A
2430 A
3200 A
3200 A
3200 A
3120 A
3040 A
2960 A
4000 A
4000 A
3930 A
n
Max. operational current at ambient temperature
25 °C
30 °C
35 °C
1870 A
1830 A
1790 A
1790 A
1750 A
1710 A
2250 A
2200 A
2150 A
2230 A
2170 A
2110 A
2840 A
2780 A
2720 A
2480 A
2420 A
2360 A
3650 A
3580 A
3510 A
n
Equipment Manual, 02/2023, 92310000002-06
40 °C
45 °C
2000 A
2000 A
1960 A
1910 A
2500 A
2440 A
2380 A
2330 A
3140 A
3070 A
2880 A
2820 A
3860 A
3790 A
≤ 1600 A, no derating needs to be
40 °C
45 °C
1750 A
1710 A
1670 A
1630 A
2100 A
2050 A
2050 A
1990 A
2660 A
2600 A
2300 A
2250 A
3440 A
3370 A
≤ 1250 A, no derating needs to be
3WA1 air circuit breaker
50 °C
1970 A
1870 A
2380 A
2270 A
3000 A
2750 A
3720 A
50 °C
1670 A
1590 A
2000 A
1920 A
2530 A
2200 A
3300 A