4.3.2

Capacitor trip device for shunt trips

4.3.2.1

Description

In the event of short-time brownouts of the supply voltage, the capacitor trip device
takes over the power supply of the shunt trips for uninterrupted duty, see Chapter
Closing coil, shunt trip, undervoltage release (Page 234).
Note
Only shunt trips with an operational voltage of 220 V to 250 V DC / 208 V to 240 V AC
can be used in combination with the capacitor trip device.
You will find more information in the operating instructions available on the internet
(https://support.industry.siemens.com/cs/ww/en/view/109793919).
4.3.2.2

Technical specifications

Rated control supply voltage U
Operating range (acc. to IEC 60947-2)
Storage time at U
Recharging time at U
Continuous power
Opening time of the circuit breaker at 100% U
Fuse protection of the control circuit: Smallest
permissible DIAZED fuse, gL, slow-response
Miniature circuit breaker with C characteristic
4.3.2.3

Article number

Capacitor trip device for shunt trips
You can purchase the accessories in the Siemens Industry Mall
(http://www.siemens.com/product?3WA9111-0AD81).
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
S
S
S
4.3 Control and signaling accessories
220 ... 250 V DC / 208 ... 240 V AC
70 ... 110% U
S
Max. 5 min
Min. 5 s
1 VA DC / 1 W AC
80 ms
S
1 A
1 A
Accessories
Article number
3WA9111-0AD81
243