Siemens SENTRON 3WA1 Manual page 265

Table of Contents

Advertisement

Supply
Input voltage
Current consumption
Required pulse length of input voltage
Recommended pulse length of input voltage
Reset time
Delay Δt of output pulse
Maximum number of control cycles per hour
Connection elements and terminals
Design of electrical connection
Connectable conductor cross-sections
Electromagnetic compatibility
Conducted or radiated emissions
Immunity in industrial environment
Ambient conditions
Operation
Transport and storage
Degree of pollution
Degree of protection
Degree of protection acc. to IEC 60529
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
4.3 Control and signaling accessories
24 V DC
110 ... 240 V AC
100 mA at 24 V DC for 100 ms
20 mA at 230 V AC for 100 ms
Current peaks (inrush) <1 A for 100 µs possible
After 100 ms <10 mA
100 ms
200 ms ... 5 s
Min. 5 s
Max. 50 ms
60
Removable/push-in connection terminal
Solid: 1.5 mm
2
Finely stranded / with end sleeve 0.75 mm
For solid AWG cable 1 x AWG16,
2 x AWG 19/20
EN 60947-1
EN 60947-2 (CISPR 11 (Group 1, Class B))
FCC Class A
Shipbuilding requirements
EN 60947-1
EN 60947-2
Shipbuilding requirements
−40 ... +70 °C
−40 ... +80 °C
3
IP20
Accessories
2
263

Advertisement

Table of Contents
loading

Table of Contents