Siemens SENTRON 3WA1 Manual page 232

Table of Contents

Advertisement

Accessories
4.2 Preparatory and concluding installation steps for the installation of internal accessories
Opening the circuit breaker and discharging the stored-energy spring
1. Check that the circuit breaker is ready to close ("OK" indication) and the stored-energy
spring is charged ("CHARGED" indication).
2. Press I / CLOSE.
3. Check that the "CLOSED" and "DISCHARGED" indications are active.
4. Press O / OPEN.
5. Check that the "OPEN" indication is active.