Digital input IN
Number
Rated voltage
Operating range
SELV/PELV
Voltage value for reliable detection of a "1"
signal
Current consumption at signal voltage of >15 V
DC
Minimum signal duration
Digital output OUT
Number of relay outputs
Contact
Make/break time
Pulse mode
SELV/PELV
Max. continuous current at 1 output active
Max. continuous current active at all outputs
Max. switching voltage
Max. switching current
Max. breaking capacity (resistive)
Switching frequency
Connectable conductor cross-sections
Design of electrical connection
Solid
Finely stranded / with end sleeve
Finely stranded
For solid AWG cable
Electromagnetic compatibility
Conducted or radiated emissions
Immunity in industrial environment
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
4.3 Control and signaling accessories
3
24 V DC
± 20%
Suitable
15 V DC
<10 mA
100 ms
5
Changeover contact
10 ms
Suitable
Suitable
5 A at 24 V DC
10 A at 250 V AC
2 A at 24 V DC
2 A at 250 V AC
300 V DC
300 V AC
7 A at 30 V DC
0.25 A at 300 V DC
10 A at 250 V AC resistive
210 W at 30 V DC
75 W at 300 V DC
4000 VA at 250 V AC
350,000 cycles at 10 A, 250 V AC, ohmic load
Removable / push-in connection terminal
0.2 ... 1.5 mm2
0.25 ... 1.5 mm2
0.2 ... 2.5 mm2
AWG24 ... AWG16
EN 60947-1
EN 60947-2 (CISPR 11 (Group 1, Class B))
FCC Class A
Shipbuilding requirements
EN 60947-1
EN 60947-2
Shipbuilding requirements
Accessories
255