Control Logic - Flow Chart - Rheem Raypak AVIA 264 Installation And Operation Manual

Gas-fired pool and spa heater
Table of Contents

Advertisement

Available languages

Available languages

Control Logic - Flow Chart

Control Logic – Flow Chart
START
Power On
Is the Display lit?
YES
Push MODE
Select "Pool" or "Spa"
MODE
MODE
Push UP or DOWN
UP
UP
arrows to adjust
Temperature
DOWN
DOWN
Is Water Setpoint and
Water Temperature
displayed?
YES
Blower "Pre-Purge"
for 45 sec
Spark
Is Water Setpoint,
Temperature and
"Heating" displayed?
YES
Unit Heating until
demand is satisfied.
Was Water
Temperature
reached?
YES
Blower "Post-Purge"
for 3 minutes
Wait for new Heat
demand
END
50
Fahrenheit (°F)
Celsius (°C)
Inlet Sensor (kΩ)
Outlet Sensor (kΩ)
Fahrenheit (°F)
Celsius (°C)
Flue Sensor (kΩ)
• Check On/Off switch (under lid on control panel)
• Check for 240 or 120 volts to the transformer
(time clock, circuit breaker, wire connections)
• Check for 24 volts to Circuit Board (P6 connector)
"Remote" and Water Temperature displayed?
If Remote mode is set to control the heater,
Exit Remote control by pressing UP + DOWN.
Is a Fault Message displayed?
NO
Check for damaged or loose wires and terminals.
In Sensor Fault
Verify sensor per "Temperature-Resistance" table:
Inlet , Outlet or
Inlet , Outlet or Vent
- Replace Sensor if readings are out of range.
Flue Sensor
Temp [Open/Short]
- Replace Ignition board if sensor readings are right.
[Open/Short]
Gas Valve
Check voltage at valve terminals. If terminals are
energized replace control boards, if not replace valve.
Flame w/o CFH
Low Voltage
Check main voltage if voltage is below 23VAC.
Check for damaged or loose wires and terminals.
Diff Sw Closed
NO
Check Blower and Air Pressure switch:
- Replace Pressure switch if failing open or close.
Diff Sw Open
- Replace Blower if operation is intermittent.
Fan Lockout
Ing Try Failure
Check Gas valve, Gas supply and spark igniter:
- Check gas supply and valve operation.
Ign 60 min Delay
- Check Igniter and wire. Replace if damaged.
Ignition Lockout
Check for damaged or loose wires and terminals.
Clock/Fireman Sw
Switch connected to safety loop is in OFF mode.
NO
Water Sw Open
Verify water flow / pressure. Clean Filter/Strainer.
Vent Sw Open
Vent switch open. Troubleshoot extractor if installed.
Hi Limit 1 Fault
Temperature Limit switch open. Verify water flow.
Hi Limit 2 Fault
Inspect internal thermostat (Unitherm Governor) and
Cabinet Temp Lm
bypass valve.
Air SW Open
Air Pressure Switch failed in operation. Verify Blower
Diff Sw Fault
operation. Check for air inlet/outlet obstructions. Verify
air pressure.
Fan Lockout
Flame Lost
Verify gas supply. Verify gas valve operation.
Flame Flickering
Cut power, verify and clean igniter rods.
Flue Over Temp
Verify obstructions. Troubleshoot extractor if installed.
Outlet Over Temp
Verify water flow. Verify gas supply and combustion.
Low Flow Fault
Verify water flow. Verify Pump operation. Adjust Flow as
High Flow Fault
necessary. Verify filter pressure and clean if needed.
Below
Temperature-Resistance
6.3
40
50
60
70
-14
4
10
15
21
open
261
199
153
119
open
26
20
15
12
Below
Temperature-Resistance
< 7.5
50
75
100
125
< -13
10
24
38
51
short
1.03
1.09
1.14
1.19
NO
YES
Above
80
90
100
110
187
27
32
38
43
86
93
73
58
46
short
9.3
7.3
5.8
4.6
short
Above
150
200
300
400
464
65
93
149
204
240
open
1.25
1.35
1.57
1.77