NEW YORK CITY (FDNY) SPECIFICATIONS
Introduction
The programming specifications contained in this section must be completed when installing Com Series Communicators
for New York City (FDNY) fire alarm IP communication applications. Refer to the FDNY Certificate of Approval #6262 for
the complete conditions of approval.
Network and Cellular Communication, Primary and Secondary
When installed as a central station Internet (Network) communicator or slave transmitter, both primary and secondary
channels of communication shall be required and shall meet the conditions below. Network communication shall be
used as the primary channel of communication to the Central Station and a Cellular Communicator shall be used as the
secondary channel of communication or in reverse order: Cellular Communicator as the primary channel and Network
connection as the secondary channel.
Network Primary And Cellular Backup Programming
NETWORK PROGRAMMING
Comm Type = NET
Checkin Min = 5
Failtime Min = 5
Test Rpt = Yes
Test Freq = 1 Dy
Cellular Primary and Network Backup Programming
CELLULAR PROGRAMMING
Comm Type = CELL
Checkin Min = 5
Failtime Min = 5
Test Rpt = Yes
Test Freq = 1 Dy
CELLULAR PROGRAMMING
Comm Type = CELL
Checkin Min = 5
Failtime Min = 5
Test Rpt = Yes
Test Freq = 1 Dy
NETWORK PROGRAMMING
Comm Type = NET
Checkin Min = 5
Failtime Min = 5
Test Rpt = Yes
Test Freq = 1 Dy