Quantech QTC40160 Installation Operation & Maintenance page 5

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form QTC4-NM2
Issue date: 05/12/2023
Base Product Type
Q = Quantech
TC = Variable Speed Screw
4 = Air Cooled Design Series
Model Number
Configuration
S = Condenser Code
X = Evaporator Code
X = Compressor Code
X = Condenser Fan
& Sound Kit Code
The Control/VSD Cabinet contains lethal
high AC and DC voltages. Before per-
forming service inside the cabinet, remove
the AC supply feeding the chiller and
verify using a non-contact voltage sensor.
The DC voltage on the VSD DC Bus will
take 5 min to bleed off, after AC power
is removed. Always check the DC Bus
Voltage with a Voltmeter to ensure the
capacitor charge has bled off before work-
ing on the system.
NEVER short out the DC Bus to dis-
charge the filter capacitors.
NEVER place loose tools, debris, or any
objects inside the Control Panel/VSD
Cabinet.
ASHRAE
Quantech
Unit nonmenclature
UNIT NOMENCLATURE
-
QTC4
210
90.1
Compliant
SXXX
46
AA
NEVER allow the Control Panel VSD
Cabinet doors to remain open if there is a
potential for rain to enter the panel. Keep
doors closed and ensure that all latches 
are engaged on each door unless the unit
is being serviced.
ALWAYS lockout the disconnect supply-
ing AC to the chiller.
The 1L Line Inductor will reach operating
temperatures of over 300°F (150°C). DO
NOT open panel doors during operation.
Ensure that the inductor is cool whenever
working near the inductor with power
OFF.
Level / Refrigerant
A = Refrigerant R-134a
B = Refrigerant R-513A
Voltage
17 = 200 / 3 / 60
28 = 230 / 3 / 60
40 = 380 / 3 / 60
42 = 400 / 3 / 60
46 = 460 / 3 / 60
50 = 380-415 / 3 / 50
58 = 575 / 3 / 60
LD23520a
Products are produced at a
f a c i l i t y w h o s e q u a l i t y -
management systems are
ISO9001 certified.
5