Table 40 - Pressure Transducer Output Voltage, Measured Signal To Return At The Transducer - Quantech QTC40160 Installation Operation & Maintenance

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Form QTC4-NM2
Issue date: 05/12/2023

Table 40 - Pressure transducer output voltage, measured signal to return at the transducer

Suction pressure transducer
(125 psig)
Pressure
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
Quantech
Voltage
0.50
0.66
0.82
0.98
1.14
1.30
1.46
1.62
1.78
1.94
2.10
2.26
2.42
2.58
2.74
2.90
3.06
3.22
3.38
3.54
3.70
3.86
4.02
4.18
4.34
4.50
Condenser liquid, discharge, and economizer pressure
transducers
Pressure
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
375
400
Section 9 - Maintenance
Voltage
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.25
3.50
3.75
4.00
4.25
4.50
183