Quantech QTC40160 Installation Operation & Maintenance page 132

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Section 8 - Micropanel
Compressor #1 run time
SYS 1 RUN TIME
XX DAYS XX HOURS XX MINUTES XX SECONDS
This message displays the system run time since the
last start in days, hours, minutes, and seconds at the
time of the fault.
System #1 run signals
SYS 1 RUN SIGNALS
RUN PERM = XXX
This message displays the system run signal relay (re-
lay output board) status, Run Permissive Input status,
and the Internal Software (microprocessor command)
ON/OFF Start status. The status of each will indicate
either ON or OFF.
System 2 data
Data for the system 2 at the time of the fault is dis-
played in the same sequence as the system #1 data.
Compressor operating hours and starts
HOURS 1=XXXXX, 2=XXXXX
START 1=XXXXX, 2=XXXXX
This message displays compressor operating hours and
compressor starts at the time of the fault.
Chilled liquid setpoint cooling setpoints
SETPOINTS
LOCAL COOLING SETPOINT
This message displays the programmed cooling
setpoint at the time of the fault.
SETPOINTS
LOCAL CONTROL RANGE
This message displays the programmed Control Range
at the time of the fault.
Remote setpoint and range
SETPOINTS REMOTE SETPOINT = XXX.X °F
REMOTE CONTROL RANGE = +/- X.X °F
This message displays the remote setpoint and control
range at the time of the fault.
132
RELAY = XXX
SOFTWARE = XXX
= XXX.X °F
= +/- X.X °F
Maximum remote temperature setpoint
SETPOINTS
MAXIMUM REMOTE TEMP RESET = XXX.X °F
This message displays the maximum remote reset pro-
grammed at the time of the fault.
Options
Display language
OPTIONS
DISPLAY LANGUAGE
◄ ►
XXXXXXXXXXXXXXXXXXXX
This message displays the language selected at the time
of the fault.
Chilled liquid cooling mode
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
WATER COOLING
This message displays the chilled liquid temperature
mode (water or glycol) selected at the time of the fault.
Local/remote control mode
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
GLYCOL COOLING
This message indicates whether Local or remote con-
trol mode was selected at the time of the fault.
OPTIONS
LOCAL / REMOTE CONTROL MODE
◄ ►
XXXXXXXXXXXXXXXXXXXXX
When remote control mode is selected, control of the
chilled liquid setpoint is from a remote device such as
a BAS controller.
Display units mode
OPTIONS
DISPLAY UNITS
◄ ►
XXXXXXXXXXXXXXXXXXXX
This message indicates whether SI (°C, barg) or
Imperial units (°F, psig) was selected at the time of the
fault.
Form QTC4-NM2
Issue date: 05/12/2023
Quantech