Checking The System For Leaks; Leak Testing; Leak Testing During Operation; Vapor Connection Locations - Quantech QTC40160 Installation Operation & Maintenance

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

Section 9 - Maintenance

Checking the system for leaks

Leak testing

The refrigerant side of the system is carefully pressure
tested and evacuated at the factory.
After the system has been charged, the system must be
carefully leak tested with a refrigerant-compatible leak
detector to ensure that all joints are tight. The accept-
able limit for a 100% pure R-134a or R-513A system is
0.1 oz/year at DWP.
If any leaks are indicated, they must be repaired imme-
diately. At times, leaks can be stopped by ensuring that
face seal nuts and flange bolts are correctly torqued.
However, for any major repair, the refrigerant charge
must be removed, and the system leak checked using
reliable methods like a pressure test.
See Removing the refrigerant charge for service on
page 169 for reference.

Leak testing during operation

After the system has been charged, the system must be
carefully leak tested with a compatible leak detector to
ensure that all joints are tight. The acceptable limit for
Callout
Component
A
Compressor discharge line isolation ball valve
C
Liquid line angle valve

Figure 64 - Service connections

160
a 100% pure R-134a/R-513A system is 0.1 oz/year at
DWP.
If any leaks are indicated, they must be repaired imme-
diately. Usually, leaks can be stopped by tightening the
O-ring face seal (ORFS) fitting, flare nuts, or flange
bolts. However, for any major repair, the refrigerant
charge must be removed.

Vapor connection locations

To be able to correctly evacuate, leak test, and charge
the QTC4 system, all the vapor connections must be
aligned correctly to conduct a correct system service.
See Figure 64 on page 160 for these locations.
Ensure that all valves in the system, in-
cluding the condenser and the economizer
EEVs manual valves and ball valves are
100% open, when any procedures such
as leak checks, evacuation, or refrigerant
handling service are being performed on
the chiller system as a whole.
Use these service valves for all vapor and charging
connection processes. This includes evacuation, vacu-
um gauge connection, vapor, and liquid charging.
Callout
Component
B
Condenser drain liquid service valve
D
Suction service valve (Optional)
Form QTC4-NM2
Issue date: 05/12/2023
Quantech

Advertisement

Table of Contents
loading

Table of Contents