Tests are to be executed according to IEC 896-2 (EN 60896-2). In addition eventual
state or local regulations may have to be observed.
C.7

Warranty

Warranty claims are subject to proper service and maintenance. In support of claims the
following documentation has to be supplied: Detailed description of fault / damage, relevant
identification data and the last maintenance reports. Faulty batteries have to be returned for
fault analysis.
i
The warranty becomes void if these handling instructions are not observed: i.e. in the
case of too high ambient temperature, the batteries being left discharged for an
extended period, inadequate storage conditions, incorrect float charge setting, failure
to maintain the recommended service intervals and service instructions.
C.8

Table of torques for the battery connectors

Type
Torque
BSOL BTX
(Nm)
(LS)
12-17
6.2
12-17 LS
6.2
12-24
6.2
12-24 LS
6.2
12-28
6.2
12-28 LS
6.2
Type
Torque
BSOL BTX
(Nm)
(LS)
12-33
8.5
12-33 LS
8.5
12-40
8.5
12-45
8.5
12-45 LS
8.5
12-55
8.5
12-55 LS
8.5
12-60
8.5
12-75 LS
8.5
12-80
8.5
12-80 LS
8.5
12-90 LS
8.5
12-100
8.5
12-100 LS
8.5
12-134
8.5
Type
Torque
BSOL BTX
(Nm)
(LS)
12-120
12.4
12-120 LS
12.4
12-150
12.4
12-150 LS
12.4
12-190 LS
12.4
12-200
12.4
12-200 LS
12.4
35