Connecting The Emergency Ciruits In A Single Monitored Sub Distribution - Zumtobel ONLITE central CPS K Installation Instructions Manual

Table of Contents

Advertisement

3.4.2
Connecting the emergency ciruits in a single monitored sub
distribution
A maximum of 20 emergency circuits can be connected to each sub distribution. Each circuit
is fused by two outgoing fuses.
1. Route the connection cables into the cabinet through the flange plate at the top side of the
switch cabinet.
2. Connect each emergency circuit to the terminal blocks -5X1 (DALI terminals and PE
terminal block) and -5X2 in the switch cabinet of the ONLITE central CPS system or the
external sub distribution (as shown in the figure below).
i
For connecting the emergency circuits of a single monitored sub distribution a 5-pin
cable is used because two DALI connections D1 and D2 must be wired additionally to
the voltage supply.
DALI connection D1 and D2
(brown/grey)
15
N (blue)
L (red)
PE
(yellow/green)