3.5 Connecting the 230 V AC / 400 V AC voltage supply

The ONLITE central CPS system is powered by the general 230 V AC / 400 V AC mains or in
emergency operation by the batteries (battery cabinet or battery rack) or an emergency
generator.
Before connecting the voltage supply, ensure that
the system and the supply lines are switched dead,
the fuses 2F1, 2F2, 2F10.1 and 2F10.2 are opened (removed).
d
Danger
When disregarding the preliminaries there is a risk of mortal danger due to live parts!
Proceed as follows to connect the ONLITE central CPS system to 230 V AC / 400 V AC
mains:
1. Switch the system dead by opening the external main switch and protect the system
against re-engagement.
2. Route the connection cables into the cabinet through the flange plate at the top side of the
switch cabinet.
3. Connect the 230 V AC / 400 V AC mains and the earth wire to the screw terminals L1, L2,
L3, N and PE of the terminal block -2X1 of the ONLITE central CPS switch cabinet.
i
When connecting the 400 V AC voltage supply, please note that the phasing (L1-L3)
corresponds to a clockwise rotating field. For this purpose a phase sequence indicator
must be used.
PE
L1
L2
L3
16
N