Current Transformer And Potential; Transformer Wire Sizing - Trane CenTraVac CDHH Installation, Operation And Maintenance Manual

Water-cooled chillers
Table of Contents

Advertisement

Current Transformer and
Potential Transformer Wire
Sizing
For customer-supplied starter-to-chiller unit control panel
starter module 1K23; these wires must be separated from
120 Vac or higher wiring.
Table 19. Maximum recommended wire length for
secondary current transformer (CT) leads in
dual CT system
Wire AWG
(a)
8
10
12
14
16
17
18
20
Notes:
1.
For AWG/MCM equivalents in mm
Requirements," p.
53.
2.
Wire length is for copper conductors only.
3.
Wire length is total one-way distance that the CT can be from the starter
module.
(a)
Wires, lugs, and fuses/breakers are sized based on National Electric Code
(NEC) [NFPA 70] and UL 1995.
CDHH-SVX003C-EN
Maximum Wire Length
Secondary CT Leads
Feet
Meters
1362.8
415.5
856.9
261.2
538.9
164.3
338.9
103.3
213.1
65.0
169.1
51.5
134.1
40.9
84.3
25.7
2
, refer to the table in
"Electrical
Customer-supplied Remote Starter Wiring
Table 20. Maximum recommended total wire length
for potential transformers (PTs) in a single
PT system
Wire AWG
(a)
8
10
12
14
16
17
18
20
21
22
Notes:
1.
For AWG/MCM equivalents in mm
Requirements," p.
53.
2.
Wire length is for copper conductors only.
3.
Wire length is maximum round trip wire length. The maximum distance
the PT can be located from the starter module is half of the listed value.
(a)
Wires, lugs, and fuses/breakers are sized based on National Electric Code
(NEC) [NFPA 70] and UL 1995.
Table 21. Maximum recommended total wire length
(to and from) for PT leads in a dual PT
system
Max Wire Length Primary
Wire AWG
(a)
Feet
8
3061
10
1924
12
1211
14
761
16
478
17
379
18
301
20
189
21
150
22
119
Notes:
1.
For AWG/MCM equivalents in mm
Requirements," p.
53.
2.
Wire length is for copper conductors only.
3.
Wire length is maximum round trip wire length. The maximum distance
the PT can be located from the starter module is half of the listed value.
(a)
Wires, lugs, and fuses/breakers are sized based on National Electric Code
(NEC) [NFPA 70] and UL 1995.
Maximum Lead Length
Feet
Meters
5339
1627
3357
1023
2112
643
1328
404
835
254
662
201
525
160
330
100
262
79
207
63
2
, refer to the table in
"Electrical
Max Wire Length
Secondary
Meters
Feet
Meters
933
711
217
586
447
136
369
281
85
232
177
53
145
111
33
115
88
26
91
70
21
57
44
13
45
34
10
36
27
8
2
, refer to the table in
"Electrical
57