Trane CenTraVac CDHH Installation, Operation And Maintenance Manual page 16

Water-cooled chillers
Table of Contents

Advertisement

Pre-Installation
Less than 1 month
Location requirements:
Solid foundation
Vibration free
Dry
Temperature range -40°F to 158°F
(-40°C to 70°C)
Do not remove any plastic coverings
Do not charge the chiller with refrigerant
If additional refrigerant is on site, follow
manufacturer's storage requirements
Verify dry nitrogen pressure using gauge
located on the evaporator shell reads
3 to 5 psig (20.7 to 34.5 kPaG)
Notify the local Trane office if charge has
escaped
Do not operate purge unit
(a)
If the chiller will be stored for more than six months after production, contact your local Trane Service Agency for required extended storage actions to minimize impact to the
chiller and preserve the warranty.
16
1–6 months
Location requirements:
Solid foundation
Vibration free
Dry
Temperature range -40°F to 158°F
(-40°C to 70°C)
Do not remove any plastic coverings
Do not charge the chiller with refrigerant
If additional refrigerant is on site, follow
manufacturer's storage requirements
Verify dry nitrogen pressure using gauge
located on the evaporator shell reads
3 to 5 psig (20.7 to 34.5 kPaG)
Notify the local Trane office if charge has
escaped
Do not operate purge unit
Verify waterbox and tube bundles are
clean and dry
Greater than 6 months
Location requirements:
Solid foundation
Vibration free
Dry
Temperature range -40°F to 158°F
(-40°C to 70°C)
Do not remove any plastic coverings
Do not charge the chiller with refrigerant
If additional refrigerant is on site, follow
manufacturer's storage requirements
Verify dry nitrogen pressure using gauge located on
the evaporator shell reads 3 to 5 psig
(20.7 to 34.5 kPaG)
Notify the local Trane office if charge has escaped
Do not operate purge unit
Verify waterbox and tube bundles are clean and dry
Conduct an oil analysis and verify no oil breakdown
Repeat yearly
Replace oil if breakdown has occurred
If no oil analysis program has been followed, replace
oil prior to start-up
(a)
CDHH-SVX003C-EN