Application Guidelines
Electric characteristics for (50Hz)
Item
Nominal output
Power supply
Electric characteristics
Min. wire size
Operation circuit wire size
Earth cable size
Earth leakage breaker
Note:
1. Electric characteristics are based on the condenser suction air temperature at 32°C, evaporation temperature -10°C and
condensing unit inlet superheat degree 10 deg.
2. Figure in [ ] of the minimum wire size shows the maximum wire length (m) with the voltage drop at 2 V.
28
AB408540130380en-000102
4. Installation
Screw size
M4
M5
M6
M8
M10
Power consumption
Operation current
Rated current
Rated sensitivity current
Tightening torque (Nm)
(Unit)
OP-UPAC015COP04E
(kW)
3P, 380/400/415 V, 50 Hz
(kW)
(A)
2
(mm
)
10 mm
2
(mm
)
2
(mm
)
(A)
(mA)
30 (Release time 0.1 sec. or less)(Class B)
1.0 ~ 1.3
2.0 ~ 2.5
4.0 ~ 5.0
9.0 ~ 11.0
18.0 ~ 23.0
6.4
10.54/10.54/10.54
17.4/16.5/15.9
2
× 4(5) (Max. length: 70m)
2.0
3.5
30
© Danfoss | Climate Solutions | 2023.02