Advertisement

Quick Links

Installation Instructions
Original Instructions
1719 Ex I/O
Catalog Numbers 1719-AENTR, 1719-IJ, 1719-IBN8B, 1719-IBN8, 1719-IF4HB, 1719-IR4B, 1719-IT4B, 1719-OB2, 1719-OB2L, 1719-CF4H, 1719-PSDC,
1719-A22, 1719-A8, 1719-A24, 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2SA, 1719-TB8x2, 1719-TB6F, 1719-TB8F, 1719-TB8x2F,
1719-CBL, 1719-ARM, 1719-SP1
Topic

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic
Added instructions on how to install a separation plate
Page
1
5
5
6
6
9
10
11
11
12
12
12
13
13
15
Page
10

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Allen-Bradley 1719 Ex I/O

  • Page 1: Table Of Contents

    Installation Instructions Original Instructions 1719 Ex I/O Catalog Numbers 1719-AENTR, 1719-IJ, 1719-IBN8B, 1719-IBN8, 1719-IF4HB, 1719-IR4B, 1719-IT4B, 1719-OB2, 1719-OB2L, 1719-CF4H, 1719-PSDC, 1719-A22, 1719-A8, 1719-A24, 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2SA, 1719-TB8x2, 1719-TB6F, 1719-TB8F, 1719-TB8x2F, 1719-CBL, 1719-ARM, 1719-SP1 Topic Page Summary of Changes Adapter Components Adapter Considerations Installing the Backplane...
  • Page 2 Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 3 • Mounting: the type of protection is “Ex nA IIC T4 Gc”, comply to Standards EN 60079-0:2012+A11:2013 and EN 60079-15:2010. Certificate DEMKO 16 ATEX 1780X. 1719-PSDC • Mounting: the type of protection is “Ex nA IIC T4 Gc”, comply to Standards EN 60079-0:2009 and EN 60079-15:2010. Certificate PF 08 CERT 1234 X. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 4 • Avoid electrostatic charges. For example, plastic parts must always be cleaned using a damp cloth, and never using a dry cloth. • Affix a warning sign that is easily recognizable to the inside of the enclosure. The sign must read as follows: “WARNING — avoid electrostatic charge”. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 5: Adapter Components

    In the Add-on Profile display, on the Module Info page, the Internal State of the adapter shows Run mode regardless of the status of the controller (Program mode or Run mode). • Modules can only be reset by inhibiting the module through the Add-on Profile. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 6: Installing The Backplane

    • Never supply a control voltage to X03.1…X03.3. On backplanes 1719-A8, output deactivation of the I/O modules can be controlled by a voltage-free contact only. • Only operate multiple adjacent backplanes using a common contact to avoid equalizing currents. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 7 2 = Base and extension backplane, which is controlled in common X02 and X01 Terminal Assignment (1719-A8) X02 Terminal Assignment X01 Terminal Assignment X02.1 X01.1 X02.2 +24V DC X01.2 +24V DC X03.3 Ground X01.3 Ground Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 8 (when used with 1719-A22 base backplane) 1719-A24 slots 9…13 14…18 19…23 24…28 29…32 (when used with 1719-A8 base backplane) S1 switch S1.1 S1.2 S1.3 S1.4 S1.5 X03 contact X03.2 X03.3 X03.4 X03.5 X03.6 Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 9: Inserting And Removing Modules

    Remove the modules by positioning your thumb and index finger on the top and bottom of the module and pulling. If necessary, adjust the information on the label carrier above the I/O modules. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 10: Installing The Separation Plate

    Hook the catch onto the label carrier at the top of the chassis. Label carrier Bottom of chassis Top of chassis Insert the pin into the plastic holder at the bottom of the chassis. The pin snaps into place Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 11: Field Wiring

    You can code the front sockets of the I/O modules and terminals so that the terminals and the associated field devices can be assigned to exactly one front socket. Use the 1719-CP coding pins for the following terminal blocks: 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2, 1719-TB6F, 1719-TB8F, 1719-TB8x2F. Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 12: Line Fault Detection

    If you operate the 1719-IR4B I/O module in a 2-wire configuration, the wire resistance amounts to that of a resistor that is connected in series to the sensor and affects the measurement result. To avoid measurement errors, the wire resistance must be measured and compensated for in this configuration. Two options are available here: Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 13: Ethernet/Ip Connection

    More information on this topic can be found in the technical literature and the applicable standards. Interference Electromagnetic fields can interfere with the communication path. Interfering signals caused by induction in parallel conductors Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 14 The same applies to galvanically isolated signals. However, unexpected results may arise in networks that are created by multichannel systems without isolation. This is because the filter capacitors may even run in parallel, depending on the setup. Isolate the channels to eliminate any interference. EMC filters in a network (simplified diagram) Rockwell Automation Publication 1719-IN001D-EN-E - November 2020...
  • Page 15: Additional Resources

    Provides 1719 Ex I/O certification information and links to control drawings. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, rok.auto/certifications Provides declarations of conformity, certificates, and other certification details.
  • Page 16 Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Allen-Bradley, expanding human possibility, FactoryTalk, Rockwell Automation, RSLinx, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.