Summary of Contents for socomec MASTERYS BC+ 10 kVA
Page 1
INSTALLATION AND OPERATING MANUAL MASTERYS BC+ 10-40 kVA...
Page 2
Ask your Socomec dealer for your activation code. Visit us at www.socomec.com for more info. (tool page). This Application is meant to support the User when installing the relevant SOCOMEC products in tutoring the installation step by step. The Application shall in no way substitute the installation and user manual provided with this SOCOMEC product, which remains the sole accurate instructions in terms of safety, handling, connection and use of SOCOMEC products.
UPS inactivity. SOCOMEC may, at its own discretion, opt for the repair of the product or the replacement of faulty or defective parts with new parts, or with used parts of equivalent quality to new parts with regard to function and performance.
CAUTION! If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact SOCOMEC. Do not operate the unit if it has suffered a violent mechanical shock of any kind. NOTE! Install the unit in accordance with clearances in order to prevent access to handling devices and guarantee sufficient ventilation (refer to 'Environmental requirements' chapter).
Page 7
For such uses we would advise you to contact SOCOMEC beforehand to confirm the ability of these products to meet the requested level of safety, performance, reliability and compliance with applicable laws, regu- lations and specifications.
In the event of contact with the eyes, wash immediately with plenty of water and call a doctor. Call a doctor immediately in the event of accidents or illness. Do not dispose of in normal waste stream (symbol waste electrical and electronic equipment). MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Failure to heed this warning could result in the unit falling over, equipment damage, injury and even death. Always use stabiliser bars if provided (see diagram below). Top heavy 640 mm MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 11
Unpacking procedures Only if stabiliser bars are provided. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
1. Connect a normally-closed early make contact from the External Maintenance bypass switch to the dedicated connector (if present) or to the ADC+SL board. 2. See 'Standard features and option' chapter. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
3. If a system shutdown switch is present, it is advisable to connect a normally open early break contact from the switch to the parallel board of the concentrator unit. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
2. For parallel configuration, cables shall have the same size and length for each unit (maximum length tolerance is ±5%). 3. Determined by the size of the terminals. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 15
UPS. Before turning on an individual unit ensure that the relevant unit output switch is closed. Before opening unit output switch ensure that the relevant unit is turned off. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Electrical contact data: 1.6 A 250 V AC. As an option the unit can be delivered with the integrated internal backfeed switches. Refer to 'Standard features and option' chapter. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
≥10 cm ≥10 cm 1. Control cables: connections between the cabinets and each unit, alarm signals, remote mimic panel, connection to the BMS (Building Management System), emergency stop, connection to generator. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
5.4 Internal front view details Option slots 1 Option slots 2 Ethernet network for service only USB connector for service only Backfeed connector MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
6. CONNECTIONS NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully. Use cables with tin-plated eyelets for the PE connection. 6.1 Earth connection M8 screw MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
To unlock the keypad the buttons must be pressed in the reverse sequence: ENTER > DOWN > UP > ESC These sequences work only on the MIMIC PANEL page. When the keypad is locked the key symbol is shown. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
ON AUTO BYPASS The output load is on static bypass UNIT AVAILABLE Energy saver is active (inverter is off temporarily) STANDBY Unit on standby LOAD OFF The output load is off MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 29
UNIT OUTPUT OUTPUT FROM STATIC SWITCH BYPASS INPUT NOTE! When in converter mode, 6 and 7 are not shown. Bar styles identify the energy flow: • solid: enabled • dotted: disabled MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 30
General alarm On maintenance bypass Bypass mode (or Eco Mode) not possible Scheduled Inspection warning: machine inspection required, call SOCOMEC support service Operating on GenSet NOTE! Available only with ADC+SL option card MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 31
> 100% Battery status Battery charging Upper level fl ashing Battery discharging Level reached is fl ashing NOTE: Battery symbol is shown only if battery Battery open available Battery alarm fl agged MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
REFERENCES ▶ UPS INFORMATION • • • ▶ SERIAL NUMBER • • • ▶ SOCOMEC REFERENCE • • • ▶ USER DEVICE REF • • ▶ USER DEV LOCATION • • MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 33
MAINS CONFIGURATION • • ▼ PARALLEL SYSTEM ▶ UNITS IN PARALLEL • ▶ REDUNDANCY LEVEL • (^). depending on setting. 1. Some menu options may not be available on some UPS models. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
8.4.5 MEASUREMENTS menu This menu displays all UPS measurements relating to the input stage, output stage, batteries and auxiliary mains (bypass). If there is more than one page press UP/DOWN to scroll pages. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
• UPS SETTINGS: critical machine settings for output, batteries and backfeed. Some parameters cannot be modified when the UPS supplies the load by INVERTER or BYPASS. Wrongly configured UPS SETTINGS could damage the load or batteries. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
• Wait approx. 2 minutes for the UPS shutdown. NOTE: the controlled shutdown of each server connected to the LAN can be managed by shutdown software. • Carry out the operations indicated on the display. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
• Carry out the operations indicated on the display. NOTE! When an external maintenance bypass is present, put the switch to position 0 (OFF). 1. Not monitored by the UPS or by the parallel system. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
This operations interrupts the supply to the output load from both inverters and automatic bypass. Remote UPS power OFF It is possible to interrupt the power supply to the output load using the ADC+SL card. Refer to 'Standard features and option' chapter. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
ECO MODE operation provides very high efficiency, since the application is powered directly from the auxiliary mains via the automatic bypass under normal operating conditions. To activate follow the correct procedure in the control panel. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instability of the GENSET and at the same time to avoid operation from the battery or risks of out-of-synchro- nisation switching on to the bypass. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Internal Backfeed Protection (3/3) Kit For Common Mains (3/1) Kit For Separate Mains (3/3) Mechanical Option Ramp for UPS unloading Kit for Front and Lateral Cover Kit for IP21 Required option MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
• Relay 1 gives the possibility of choosing between normally closed (NC1) or normally open (NO1) position. Relays 2, 3 and 4 only have normally open position (NOx). • On connector , Cx means common, NOx means normally open position. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 43
1. The acronyms mentioned are linked to MODBUS table (Snnn=Status/Annn=Alarm). 2. A self-locking emergency push button must be used for the UPS Power Off input. Note: custom configuration is also available. For more information contact Socomec. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
NOTE! Inputs and relays can be re-programmed depending on requirements. Contact your SOCOMEC after-sales service to change Input/Output programming. Information coming from inputs can be reported in the UPS database for display on the mimic panel and is accessible on the MODBUS table.
(MODBUS TCP - IDA). 11.5 BACnet card With the BACnet card fitted in the options slot, the UPS can be monitored from remote stations using the appro- priate protocol (BACnet - IDA). MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Available only with ADC+SL option card. 11.7 PROFIBUS protocol interface Socomec UPS can be provided with an interface of PROFIBUS ® DP slave type for the UPS to be connected to a PROFIBUS ® PLC. PROFIBUS ® protocol is aimed at exchanging data between input/output monitoring devices and a master unit.
Cabling errors with inversion between phase and neutral conductors may cause permanent damage to the equipment. Input/ Battery Details Output type phases 10-15-20 Internal OUTPUT INPUT battery L1 L2 L3 L1 L2 L3 L1 L2 L3 MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
A PEN conductor is prohibited in the case of unbalanced and third harmonic current circulation. TN-C-S connection TN-C connection Input mains Input mains Auxiliary mains Auxiliary mains Output Use the same Neutral PEN section of the power connections. 11.14 Ramp for UPS unloading MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Please contact the Service Dept. The input mains supply is out of tolerance. Verify that the input A035 RECTIFIER INPUT SUPPLY NOT OK voltage and frequency are within the UPS ratings. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
NOTE: servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions. NOTE: when replacing batteries, replace with the same type and number of batteries or battery packs. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
(premises, usage or load type) are abnormal or harsh for the equipment. It is advisable to replace consumables as follows Consumable part Years AC and DC capacitor 1. Based on operation of the unit according to the manufacturer’s specification. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
For any questions regarding the disposal of the product, contact local distributors or retailers. In case of product with incorporated battery, please use the proper recycling. MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
, AS 62040-2 Product certification CE - IECEE CB Scheme Product marks RCM - EAC - CMIM Protective class Protective Class I Touch current < 1 mA Protection level IP20; IP21 (option) MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC...
Page 56
1. 360 V with Pout = 90% Pn. 2. Initial Condition Pout ≤ 80% Pn. 3. @ Battery Fully Discharged. Call SOCOMEC support service. 4. @ Battery Fully Charged. Call SOCOMEC support service. 5. With output cables shorter than 10m, only for the 10 kVA 3ph output models.
Page 60
Sales offi ces CORPORATE HQ CONTACT: SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE www.socomec.com *IOMMASBCXX0G-EN 02* IOMMASBCXX0G-EN 11.2020...