Finishing

A. Facing Material
WARNING! Risk of Fire!
ered with non-combustible materials only.
• Firebox metal front faces may be covered with non-
combustible facing and/or finishing materials up to a
maximum thickness of 3 inches.
• Facing and/or finishing materials must not interfere with
air flow through the front of the firebox.
• Facing and/or finishing materials must never overhang
into the firebox opening.
• See Figures 7.1 and 7.2 for combustible and non-
combustible mantle and mantle leg clearance
requirements.
• Maintain all listed clearances when applying combustible
materials.
• Seal joints between the finished wall and firebox top and
sides using a 300º F minimum sealant.
Combustible/Noncombustible Mantels
Gray area is
combustible
material
Seal joint with
non-combustible
sealant to
prevent heat
from being
drawn into the
wall cavity.
Note: Reducing clearances further requires non-combustible construction materials (eg: steel studs, durock, etc) to a height of 12 inches above the framing height.
Figure 7.1
Minimum Vertical and Maximum Horizontal Dimensions of Combustible and Noncombustible
16
Outdoor Lifestyles • VOFB36/42 Installation Manual • 4153-901 • Rev B • 04/23
Metal front faces may be cov-
5"
4"
3"
2"
1"
5"
1"
2"
3"
4"
WARNING! Risk of Fire!
terials beyond the minimum clearances. Comply with all
minimum clearances to combustibles as specified in this
manual. Overlapping materials could ignite and may inter-
fere with proper operation.
NOTICE:
Surface temperatures around the firebox will
become warm while the firebox is in operation. Ensure
finishing materials used for all surfaces (floor, walls, mantels,
etc.) will withstand temperatures up to 190°F.
B. Mantel and Wall Projections
WARNING! Risk of Fire!
ances as specified.
Reducing non-combustible mantel and/or mantel leg
clearances closer than those listed in this manual
requires the use of non-combustible construction
materials (eg: steel studs, concrete boards, etc.) to a
minimum height of 12 inches (305 mm) above the listed
framing height.
Note: Mantel Measurement is taken from top of
the firebox opening, NOT the top of the unit.
18 in. Maximum
14"
13"
12"
11"
10"
9"
8"
7"
6"
14"
13"
White area is
12"
non-combustible
11"
material
10"
9"
8"
7"
6"
(Combustible
Measured from top of appliance opening
DO NOT apply combustible ma-
Comply with all minimum clear-
18"
17"
16"
15"
20 in.
18"
17"
16"
15"
14 in.
3 in.
Min.
Mantle)