V
ECTOR

Mounting and Installation

Mounting location
In a cabinet on a flat surface
In a cabinet on a top-hat rail
In a panel (cabinet door) with the optional panel mounting kit
The following mounting locations should be avoided:
For the types with wireless transmission (-WEM or -WEB), avoid locations that interfere with the radio signals,
o
e.g. metal boxes or devices that generate electrical interferences.
Mounting instructions
See the TCI2 installation sheet, document no. 70-00-0688 or 70-00-0893 (www.vectorcontrols.com).
Selection of sensors and actuators
Temperature sensors
Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10 (room), SDB-Tn10-20 +
AMI-S10 as immersion sensor.
Actuators
Choose modulating actuators with an input signal type of 0-10 VDC or 4-20 mA (min. and max. signal limitations may be set
with parameters).
3-point actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc.)
Do not directly connect devices that exceed specified limits in technical specifications – observe start up current on inductive
loads.
Connection diagram
Type: TCI2-204.202
24V AC/DC
N
L
L
N
GND V+
DO1 DO1 DO2 DO2
24V AC/DC
Relays 3A
3 VA
Power
Digital Output (2x)
Status LED
Analog
Output (2x)
Universal Input (4x)
NTC 10k , Pt1000
0...10 VDC,
0...10 VDC, 0...20 mA
0...20 mA
GND UI1 UI2
UI3
GND
UI4 AO1 AO2
GND UI
GND
UI
GND
UI
GND
NTC
0...10 VDC
10k 
0...20 mA
PT1000
Doc: 70-07-0703B, 20220426
Subjects to alteration
Shielded Twisted Pair (STP)
N
120 Ω
Line Termination (LT)
(LT)
_
+
(-MOD) (-BAC)
RS485
Operation
Terminal
JP7
OP1
OP2
OP3
+
Vop
AO
A c t u -
1
2 3
a t o r
OPXX-VC
OPT1-xx
OPA2-xx
© Vector Controls LLC, USA
www.vectorcontrols.com
Note:
Power GND ≠ TX REF
Do not use shield as REF
RS-485
TX1 TX2
-BAC
REF
REF
BACnet MS/TP
-MOD
REF
MODBUS
TCP/IP
-ETM, -ETB
120 Ω
Ethernet Connection
OP4
-WEM, -WEB
_
WIFI Connection
STP
4
P
RODUCT
85..264 VAC
N
L
TX3
_
N
L
+
_
85..264 VAC
+
3 VA
(D0) (D1)
Power
GND
TCI2
D
S
ATA
HEET
DO1 DO1
Page 5-10